Note:
- Splice and isolate the cable shield drains at all of the subordinate devices on the
network trunk.
- You must connect the cable shield to the ground at one point along the daisy chain
only, typically at the master device.
Figure 26: Network devices in an RS485 daisy-chain configuration
Table 27: Network devices in an RS485 daisy-chain configuration
Callout
Description
1
EOL terminating device on the RS485 network trunk
2
Daisy-chained devices on the RS485 network trunk
3
Isolated shield connection terminal
4
To the next device on the RS485 network trunk
5
220 ohm EOL resistor
Connecting the EOL resistor
The following figure shows an example of ADPT-MR5-RS485 adapters in a daisy chain. The
terminating adapters in this example have EOL configuration. To configure a controller as an
EOL device, connect the 220 ohm metal film resistor (MFR) (1/2 W) to the + and - terminals on the
adapter in parallel with the RS485 network wires on the adapter.
59
MR5 Series Panel Mount Case Controller Technical Bulletin