background image

Models:

P-7 1/2-HF

P-10-HF

P-15-HF

Penguin Pumps are designed to handle a large range of chemicals without difficulty. Completely 

constructed of CPVC where in contact with the solution being pumped, Series P-HF pumps have 

an upper working temperature of 180 degrees and thus can handle slurries, and most corrosive 

and abrasive solutions. Series P-HF pumps are easy to install and operate, and are virtually 

maintenance-free. All pumps have been tested for proper operation before leaving the factory. To 

obtain optimum service life, please follow all installation and operating instructions.

Model P-7 1/2-HF

    I n s t a l l a t i o n   &   M a i n t e n a n c e

P E N G U I N

P E N G U I N

Materials:

A - CPVC

Series P-HF

ELECTRICAL

PLUMBING

LIQUID LEVEL

PRIMING

The correct liquid level is very important. A liquid level which is too high 

could cause motor damage. A liquid level that is too low, below the wear 

ring, may cause severe impeller damange, THIS PUMP CANNOT RUN 

DRY. CHECK THE LIQUID LEVEL. The correct liquid level is halfway 

between the bung hole and the centerline of the discharge nozzle.

Under flooded conditions, open all the valves in the suction and 

discharge lines. Wait a few minutes to let entrapped air out. Throttle the 

discharge valve 2/3 closed. Leave suction valves wide open. A closed 

suction or discharge valve could cause damage to the impeller and the 

shaft. Start the pump and open the valve to the desired flow. Under 

non-flooded conditions, fill up the pump slowly from the T-connection 

and valve. See recommended installation. Then throttle the discharge 

valve 2/3 closed. Start the pump and continue as flooded conditions.

Installation & Operating Instructions

PLUMBING CONTINUATION

HIGH FLOW VERTICAL PUMP 

All models are supplied with three phase dual voltage, 208-230/460V, 

50/60c motors, which are not wired at the factory. When changing from 

230V wiring to 460V wiring, follow the motor manufacturers wiring instruc-

tions, which can generally be found either on or in the motor junction 

box. Check rotation of external fan by removing splash shield, fan spins 

clockwise. It is imperative that the motor rotation be checked before op-

eration. Attach leads to motor and bump start for a maximum of a couple 

of seconds as if you were turning a light switch on/off as fast as possible. 

Do not leave motor running. As viewed from the suction entrance of the 

pump, check for counterclockwise rotation. If clockwise rotation, change 

any two hot leads and again check rotation. Replace fan splash shield. 

Many options are available on the P-HF Series motors including larger 

horsepowers to 15 and 575V motors. If any of these options are required, 

please check the motors carefully or consult the factory.

The suction side piping of the pump is extremely important. Mistakes 

can usually be compensated for if made on the discharge piping. 

However, piping problems on the suction side can be, and usually are, 

the source of ongoing problems. If a suction line or suction extension 

is required enlarge the suction line/extension by one size larger than 

the suction entrance. Never reduce plumbing on the suction. Avoid 

90-degree elbows and never use a 180-degree elbow. The suction 

piping needs to be arranged in such a way as to allow a straight, even 

flow of liquid into the eye of the impeller. This requires that all elbows, 

valves, or strainers be located at a straight and uninterrupted distance 

equal to at least 5-10 times the pipe diameter. Remember, elbows 

create turbulence and air entrapment. Make sure every suction 

coupling/connection is airtight. The bottom of the suction extension 

should always be at least 2 pipe diameters above the bottom of the 

tank. In either flooded suction or non-flooded suction conditions, the 

use of a check valve on the discharge of the pump is recommended. 

In the case of a non-flooded suction, a flapper check valve on the end 

of the submerged suction line must be installed. To facilitate priming the 

pump, install a T-connection with a small valve between the pump case 

and check valve. It is advisable to use a discharge valve after the check 

valve. All plumbing and accessories must be supported other than by 

the pump, in order to prevent possible distortion of the pump case. The 

use of some hose in the discharge plumbing close to the discharge 

nozzle of the pump will absorb any movement of the solid plumbing if 

vibrations exists. Also a good rule of thumb is that the source solution 

tank volume should be three times the flow rate of the pump.

Series P-HF_D_01-15

Reviews: