background image

                  I n s t a l l a t i o n   &   M a i n t e n a n c e

P E N G U I N

P E N G U I N

MODELS

MTD-5 

MTD-7-1/2

MTD-10

Series MTD

Magnetic Drive Pump

MATERIALS

B   - Polypropylene

C   - PVDF (Kynar)

Penguin magnetic-driven pumps are designed to handle a large range of chemicals without diffi  culty. Constructed of polypropylene, kynar, 

Series MTD pumps have an upper working temperature of 190/220/250 degrees, respectively, and thus can handle highly corrosive or mild 

chemicals, acids or solvents. Series M pumps eliminate the conventional shaft seal found in most pumps. This means that there is no rotating 

seal to wear out and allow the liquid being pumped to leak out. The pumping action may eventually fail, however, the liquid can never leak 

out. Series MTD pumps are easy to install and operate, and are virtually maintenance free. All pumps have been tested for proper operation 

before leaving the factory. To obtain optimum service life, please follow all instructions.

Install the pump as close as possible to the liquid reservoir from which the liquid is being pumped.  As more energy is necessary to prime the liquid than to 

discharge the fl uid, make the suction as short as possible.

Always make sure there is enough liquid in the reservoir and the level is high enough considering the capacity of the pump unit. Inadequate liquid will cause 

vortex in the reservoir. A vortex occurs when air mixes from the surface into the fl uid. This can disturb the fl ow and also prevents the pump from priming. 

Never run the pump for more than 5-10 minutes against a closed discharge valve. This will cause overheating of the fl uid in the pump and will damage the 

polypropylene parts. Temperature in this case will increase up to 220 degrees. If the pump is being run against a closed discharge valve for a long duration 

of time, install a small bleed line back into the reservoir before the discharge valve of the pump. If the line is small, there is a minimum pressure loss. This 

prevents overheating by recirculating the fl uid.

Model MTD pumps are supplied as standard in a single phase, single voltage, 115V, 50/60c motor with 230V as an option. All other models supplied with a 

single phase are dual voltage, 115/230V motors. The factory wires all dual voltage motors for the lower voltage (115V) unless otherwise requested. When 

changing from 115V wiring to 230V wiring, follow the motor manufacturer’s wiring instructions, which are found in the motor junction box or motor label. Be sure 

to wire the motor for clockwise rotation as viewed from the suction entrance of the pump. A power cord and plug are supplied for immediate plug-in operation 

on motors wired for the lower voltage. These motors have already been wired at the factory for proper rotation. A plug is not supplied on motors wired 230V. 

Motors supplied in three-phase are dual voltage, 230/460V, 50/60c which are not wired at the factory. Since direction of rotation cannot be determined without 

operating the pump, the motor rotation must be checked before operation. Attach leads to motor and bump start. Since these pumps must not run dry for more 

than 10 seconds, do not leave motor running. As viewed from the suction entrance of the pump, check for clockwise rotation. If counterclockwise rotation, 

change any two leads and check rotation again. Many options are available on the M Series motors including explosion-proof and special voltage motors. If 

any of these options are required, please check the motors carefully or consult factory.

It is recommended to enlarge the suction line a minimum of one size larger than the suction entrance. Never reduce plumbing on the suction. Avoid 90 degree 

elbows and never use a 180 degree elbow. Make sure that every suction coupling/connection is airtight. Always use a valve on the discharge of the pump. 

In case of a fl ooded suction, in which the liquid level is higher than the center of the suction entrance, provide a T-connection with a small valve after the 

discharge valve to assist in letting the air out during fl ooding. In case of a non-fl ooded suction, in which the liquid level is lower than the center of the suction 

entrance, provide a foot valve on the end of the submerged suction line.

  ELECTRICAL

  PLUMBING

  RECOMMENDATIONS

  INTRODUCTION

Summary of Contents for MTD Series

Page 1: ... are supplied as standard in a single phase single voltage 115V 50 60c motor with 230V as an option All other models supplied with a single phase are dual voltage 115 230V motors The factory wires all dual voltage motors for the lower voltage 115V unless otherwise requested When changing from 115V wiring to 230V wiring follow the motor manufacturer s wiring instructions which are found in the moto...

Page 2: ...drive magnet and impeller assembly away from metal chips or particles items with magnetic stripes like credit cards and magnetic computer media such as floppy discs and hard drives WARNING When pumping flammable or combustible liquids with a MTD Series pump it is important to follow these guidelines 1 You must use a PVDF pump PVDF has conductive carbon fibers added which allow it to be grounded wh...

Page 3: ...ischarge Before operating the pump ensure the electrical continuity throughout the pumping system and earth ground is 1 Ohm or less If greater than 1 Ohm re check all grounding connections Elastomer Selection Proper o ring material must be chosen for the fluid being pumped Improper material selection could lead to swelling and be a possible source of leaks This is the responsibility of the end use...

Page 4: ...he flow rate to drop below the minimum flow rate listed in the chart below Cleaning The pump must be cleaned on a regular basis to avoid dust build up greater than 5 mm Motor Rotation Test Pump must be full of liquid with no trapped air in the suction and discharge lines before the rotation of the motor is checked Do not operate pump until it is full of liquid Start Up The pump must be filled from...

Page 5: ...7 0 mm 1 8 4 5 114 0 mm 1 8 2900 rpm 50 Hz Closed Impeller Diameter Maximum Specific Gravity 184 2 mm 7 25 1 35 177 8 mm 7 1 6 165 1 mm 6 5 1 5 152 4 mm 6 1 8 139 7 mm 5 5 1 8 127 0 mm 5 1 8 3450 rpm 60 Hz Open Impeller Diameter Maximum Specific Gravity 6 152 4 mm 1 5 5 5 139 7 mm 1 8 5 127 0 mm 1 8 4 5 114 0 mm 1 8 2900 rpm 50 Hz Open Impeller Diameter Maximum Specific Gravity 181 0 mm 7 13 1 35 ...

Page 6: ...Assembly Installation and Operation MTD 5 MTD 7 1 2 MTD 10 6 ...

Page 7: ...Motor Electrical Maintenance Installation MTD 5 MTD 7 1 2 MTD 10 7 ...

Page 8: ...Disassembly Reassembly MTD 5 MTD 7 1 2 MTD 10 8 ...

Page 9: ...9 Disassembly Reassembly MTD 5 MTD 7 1 2 MTD 10 ...

Page 10: ...10 Disassembly Reassembly MTD 5 MTD 7 1 2 MTD 10 ...

Page 11: ...106764 Housing o ring EPDM opt MTD 106765 6 1 Barrier MTD 106400 MTD 106400 1 MTD 106400 MTD 106400 1 MTD 106400 MTD 106400 1 7 1 Motor adaptor standard MTD 106414 1 MTD 106414 2 MTD 106414 1 MTD 106414 2 MTD 106414 1 MTD 106414 2 Motor adaptor w non sparking ring optional MTD 106794 MTD 106794 1 MTD 106794 MTD 106794 1 MTD 106794 MTD 106794 1 7A 1 Front motor adaptor o ring Buna N standard MTD 10...

Reviews: