VISION
100
THR
Page 9
USE AND MAINTENANCE MANUAL
Rev. 02-18
TECHNICAL FEATURES
Power supply
Voltage
230 V~
10% 50/60Hz
Max. absorbed power (electronic control only)
~ 8 VA
Climatic Conditions
Work temperature
-5 ÷ +50 °C
Storage temperature
-10 ÷ +70 °C
Ambient relative humidity
Below 90% Hr
Main Features
Type of connectable probes (temperature)
NTC 10K 1%
Resolution (ambient temperature)
0.1°C
Probes reading precision (ambient temperature)
± 0.5°C
Reading range
-45 ÷ +45 °C
Humidity probe
analogical input 4-20 mA
Humidity probe reading precision
see humidity probe features
Humidity probe reading range
0-99 Hr%
Output features
Description
Installed relay
Board output features
Notes
Cold (output 3-4)
(Relay 30A AC1)
10A 250V
~
(AC3)
(
2HP)
(100000 cycles)
All outputs are clean
contacts without
voltage
9 outputs from 5 to 21
(see connections layout)
(Relay 16A AC1)
16A 250V
~
(AC1)
Dimensional features
100N MASTER Dimensions
121.50mm x 71mm x 175mm (HxDxL)
VISION100 THR Dimensions (fitted)
70mm x 32mm x 158mm (HxDxL)
Mechanical and insulation features
Display protection degree
IP65
Box material
Self-extinguishing ABS
CHAP. 3 - Technical features
CHAPTER 3: TECHNICAL FEATURES
3.1