USE AND MAINTENANCE MANUAL
Rev. 02-18
5.
Memorisation of the amendments made to the variables will happen automatically when
exiting the configuration menu. Exiting from the menu happens spontaneously after an
inactivity period or by simultaneously pressing keys
(
)
and
(
)
for a few seconds.
VARIABLES
MEANING
VALUES
DEFAULT
tdS
Day phase start time.
Germination lights active only during the
day phase.
00:00 ÷ 23:50
(10 min steps)
0
tdE
Day phase end time.
tdE can also be < of tdS; for example, a
day phase can start at 10pm and end at
4pm of the following day.
00:00 ÷ 23:50
(10 min steps)
0
tt1
t1 Temperature SET start time.
00:00 ÷ 23:50
(10 min steps)
0
tt2
t2 Temperature SET start time.
00:00 ÷ 23:50
(10 min steps)
0
t1
Temperature 1 SET.
-45,0 ÷ +45,0 °C
0,0°C
t2
Temperature 2 SET.
-45,0 ÷ +45,0 °C
0,0°C
ELECTRONIC CONTROLLER VISION100 THR IGNITION
After having wired the electronic controller, apply voltage 230Vac; the control will
immediately and simultaneously emit a sound for a few seconds and remain fully switched-
on on the display.
COLD / HOT: AMBIENT TEMPERATURE MAINTENANCE
The cold and hot call is managed in neutral area depending on the set temperature
setpoint (
key 4) and on the temperature differentials (parameters dtC and dtF). The
cold is activated upon exceeding of set + dtF and remains active until set is reached (with
dtn=0). The hot is activated below set - dtC and remains active until set is achieved (with
dtn=0).
It is possible to set a "dead area" with dtn parameter that deactivates hot and cold when
the temperature is between SET-dtn and SET+dtn.
5.13
5.14
CHAP. 5 - Data programming