Pego VISION100 THR Use And Maintenance Manual Download Page 16

             

VISION

100

 THR

  

   

Page  16 

USE AND MAINTENANCE MANUAL

 

Rev. 02-18 

 
 

 
 
 

F5 

Fans pause

 after defrosting (minutes) 

Enables  keeping  the  fans  still  for  an 

F5

  time  after  dripping. 

This  time  starts  from  the  end  of  dripping.  If  dripping  is  not 
set, the fans pause at the end of defrosting. 

 

0 ÷ 10 min 

 

0 min 

At1 

Minimum temperature alarm

 

Enables  defining  a  minimum  temperature  value  to  the 
ambient.  Below  value 

At1

,  the  alarm  state  will  be  signalled 

by  the  alarm  icon  flashing,  the  displayed  temperature 
flashing  and  an  internal  buzzer  acoustically  signalling  the 
existence  of  the  anomaly.  The  alarm  is  signalled  after  the 
Ald time. 

-45 ÷ At2-1 °C 

-45°C 

At2 

Maximum temperature alarm

 

Enables  defining  a  maximum  temperature  value  to  the 
ambient.  Above  value 

At2

,  the  alarm  state  will  be  signalled 

with  the  alarm  icon  flashing,  the  displayed  temperature 
flashing  and  an  internal  buzzer  acoustically  signalling  the 
existence  of  the  anomaly.  The  alarm  is  signalled  after  the 
Ald  time.  The  alarm  does  not  suspend  any  defrosting  in 
progress. 

At1+1 ÷ 45 °C 

+45°C 

AU1 

Minimum humidity alarm

 

Enables  defining  a  minimum  humidity  value  to  the  ambient 
to be  humidified.    Below  the  AU1  value, the  Eu  alarm  state 
will be signalled with the alarm icon flashing and the buzzer 
active.  Silencing,  the  humidity  and  the  alarm  icon  remain 
flashing. The alarm is signalled after the time (Ald).

 

1 ÷ AU2-1 Rh%

 

1 Rh% 

AU2 

Maximum humidity alarm

 

Enables  defining  a  maximum  humidity  value  to  the  ambient 
to be  humidified.    Below  the  AU2  value, the  Eu  alarm  state 
will be signalled with the alarm icon flashing and the buzzer 
active.  Silencing,  the  humidity  and  the  alarm  icon  remain 
flashing. 
The alarm is signalled after the time (Ald). AU2=99 does not 
signal the alarm.

 

AU1+1 ÷ 99 Rh%  99 Rh% 

rA 

Air change enabling in real time

 

With rA=1 it is possible to set up to 6 air changes in real time 
during one day, through parameters rA1…rA6.

 

0 = Disabled 

1 = Enabled 

rA1 

… 

rA6 

Air change times programming

 

It  is  possible  to  set  up  to  6  times  for  the  air  changes.  The 
previous  value  locks  the  subsequent  one  making  them 
sequential. 

 

00:00 ÷ 23:50 

-- 

drA 

Air change duration

 

0 ÷ 10 min 

min 

6 min 

 

tEu 

 

Evaporator probe temperature display  

(if dE =1 nothing is displayed) 

temperature 

read only 

CHAP. 5 - Data programming 

Summary of Contents for VISION100 THR

Page 1: ...Use and maintenance manual ELECTRICAL BOARDS FOR REFRIGERATING INSTALLATIONS READ AND KEEP REV 02 18 ENG VISION100 THR ENGLISH...

Page 2: ...VISION100 THR...

Page 3: ...5 8 First level variables list Page 17 5 9 Second level programming Page 17 5 10 Second level variables list Page 20 5 11 Automatic programmes Pr1 Pr2 Pr3 Pr4 Pr5 Page 22 5 12 Germination day night c...

Page 4: ...able programmes each of seven phases APPLICATIONS Seasoning and drying cells Germination cells with day night phases Preservation cells with or without humidity control MAIN FEATURES Back lit LCD disp...

Page 5: ...rial processes Complete with VISION THR and 100N MASTER THR display OVERALL CLEARANCES Dimensions in mm IDENTIFICATION DATA The equipment described in this manual is provided with an identification da...

Page 6: ...ng the wiring assuming the spiral shape damaging for possible inductive effects on the electronics 5 All conductors used in the wiring must be suitably proportioned to support the load to be powered 6...

Page 7: ...Position the module 100N MASTER on the DIN guide and close the 2 lower hooks to lock it on the same Fig 2 Fix the VISION THR console using the two screws to be inserted in the slots underneath the key...

Page 8: ...vation deactivation Probes alarms signal Air change control parameters adjustment Defrosting parameters adjustment Refreshments parameters adjustment Fans parameters adjustment Outputs state displayin...

Page 9: ...ogical input 4 20 mA Humidity probe reading precision see humidity probe features Humidity probe reading range 0 99 Hr Output features Description Installed relay Board output features Notes Cold outp...

Page 10: ...sed when the equipment is modified or transformed Under no circumstances Pego S r l will be liable for any loss of data and information costs of goods or substitute services damage to property people...

Page 11: ...gram in progress TIMER by pressing the key once it displays remaining time of phase in execution UP MANUAL REFRESHMENT and DEFROSTING activates both functions STAND BY plant ON OFF the program in prog...

Page 12: ...02 18 DOWN MUTE ALARM AIR CHANGE FORCING CELL LIGHT LED DISPLAY 1 PHASE 0 Advance Dripping Germination day phase 2 PHASE 1 advancement 3 PHASE 2 advancement 4 PHASE 3 advancement 5 PHASE 4 advancement...

Page 13: ...rameters value error codes 10 Time date time parameters values program in progress timer 11 PRG Programming control is in programming phase 12 Cold flashing if only called for dehumidification 13 Hot...

Page 14: ...mming exit current programming first SYMBOLS For practicality we will use the following symbols the UP key that performs value increase functions and forcing of defrosting refreshing the DOWN key that...

Page 15: ...emperature SETPOINT dtn 0 2 10 C 2 0 C dtn NEUTRAL temperature area referred to main SETPOINT Cold and hot are not activated in neutral area it symmetrically includes an upper part hot and a lower par...

Page 16: ...1 45 C 45 C AU1 Minimum humidity alarm Enables defining a minimum humidity value to the ambient to be humidified Below the AU1 value the Eu alarm state will be signalled with the alarm icon flashing...

Page 17: ...lly when exiting the configuration menu 6 Press the STAND BY key to enable the electronic control SECOND LEVEL VARIABLES LIST Installer Level VARIABLES MEANING VALUES DEFAULT AC Microdoor input state...

Page 18: ...o stops the fans if they are not active for other functions 0 15 min 0 dEU Dehumidification mode selection The separate dehumidification calls hot and cold only for temperature 0 cooling 1 heating 2 s...

Page 19: ...ormed Counting starts at every new dehumidification request 0 min 4 hours 1 min steps 0 Disabled 0 dEo Operation to be performed in case limit Timeout for dehumidification dEt intervenes dEO 0 an alar...

Page 20: ...T STOP and SET pressed for a few seconds the function is active only if Cg 0 1 Using key or key select the program to be amended After having selected the program press the SET key to display the para...

Page 21: ...phase evaporator fans speed Amends the value of 2nd level variable F8 0 High speed 1 Low speed only if rin 1 0 tSg Dripping phase duration 0 00 99 30 at 30 min steps 0 00 St1 Phase 1 temperature setpo...

Page 22: ...nt 0 NO 1 YES 0 v5 Phase 5 evaporator fans speed Amends the value of 2nd level variable F8 0 High speed 1 Low speed only if rin 1 0 t5 Phase 5 duration 0 00 99 30 at 30 min steps 0 00 St Seasoning pre...

Page 23: ...00 23 50 10 min steps 0 t1 Temperature 1 SET 45 0 45 0 C 0 0 C t2 Temperature 2 SET 45 0 45 0 C 0 0 C ELECTRONIC CONTROLLER VISION100 THR IGNITION After having wired the electronic controller apply v...

Page 24: ...ivated upon exceeding of set dUd and remains active until set is reached with dUn 0 Humidification is activated below set dUU and remains active until set is reached with dUn 0 It is possible to set a...

Page 25: ...s of the second level programming F3 F4 F6 F7 F8 enable setting fans management in the different modes By setting parameter rin 1 it is possible to differentiate high and low speed of the fans in the...

Page 26: ...op To manually activate defrosting it is sufficient to press the UP key Defrosting is not activated in case the temperature set for defrosting end d6 is lower than the temperature detected by the evap...

Page 27: ...on If password is forgotten use universal number 100 AUTOMATIC PROGRAMS An automatic program is a work cycle made of a maximum of 7 phases in which it is possible to automatically amend the temperatu...

Page 28: ...program execution it is possible to amend the humidity and temperature setpoint directly from the keyboard without having to access programming Variations are provisional and do not alter the pre set...

Page 29: ...of the parameters indicated in paragraph 5 12 it is possible to determine the day start and end times and manage two differential temperature setpoint During the day phase the germination lights are s...

Page 30: ...MONITORING SYSTEM To insert the board in a TeleNET network refer to the layout below To configure the instrument refer to the TeleNET manual IMPORTANT During configuration select Instrument PLUS 100 T...

Page 31: ...arged battery alarm Replace the Console lithium battery CR2032 type Ec Main alarm e g Thermal protection or max pressure switch All outputs are deactivated except the alarm output if present Check com...

Page 32: ...EMC 2014 30 EU LA CONFORMITA PRESCRITTA DALLA DIRETTIVA E GARANTITA DALL ADEMPIMENTO A TUTTI GLI EFFETTI DELLE SEGUENTI NORME THE CONFORMITY REQUIRED BY THE DIRECTIVE IS GUARANTEED BY THE FULFILLMENT...

Page 33: ...2 V 31 Y 15 16 Refreshment rin 0 low speed fans rin 1 Step 1 germin lights Cg 1 27 28 Ambient NTC probe 13 14 Air change Digital inputs section 11 12 Humidification 45 50 Stand by forcing 9 10 Cell li...

Page 34: ...VISION100 THR Page 34 USE AND MAINTENANCE MANUAL Rev 02 18 NOTES...

Page 35: ...VISION100 THR Page 35 USE AND MAINTENANCE MANUAL Rev 02 18 NOTES Attachments...

Page 36: ...entina 6 b 45030 Occhiobello ROVIGO ITALY Tel 39 0425 762906 Fax 39 0425 762905 e mail info pego it www pego it AFTER SALES ASSISTANCE CENTRE Tel 39 0425 762906 e mail tecnico pego it Distributor PEGO...

Reviews: