FIRST LEVEL PROGRAMMING (User level)
To access the first level configuration:
1.
Keep the keys
(
)
and
(
)
pressed simultaneously for a few seconds until the first
programming variable appears on the display.
2.
Release the keys
(
)
and
(
)
.
3.
Using the
(
)
key or
(
)
key, select the variable to be amended.
4.
After having selected the wanted variable, it will be possible:
• To display its setting by pressing the SET key.
• Amend its setting by keeping the SET key pressed and by pressing one of the
(
)
or
(
)
keys. To exit the menu once the configuration values are set, simultaneously keep the
(
)
and
(
)
keys pressed for a few seconds, until the cell temperature value appears
again.
5.
Memorisation of the amendments made to the variables will happen automatically when
exiting the configuration menu.
FIRST LEVEL VARIABLES LIST (User Level)
VARIABLES
MEANING
VALUES
DEFAULT
dtC
HOT temperature differential
referred to main SETPOINT.
It is expressed in absolute value and defines the
temperature hysteresis for HOT referred to temperature
SETPOINT.
(dtn+0.2) ÷ 10 °C
2,0 °C
dtF
COLD
temperature
differential
referred
to
main
SETPOINT. It is expressed in absolute value and defines the
temperature hysteresis for COLD referred to temperature
SETPOINT.
(dtn+0.2) ÷ 10 °C
2,0 °C
dtn
NEUTRAL temperature area
referred to main SETPOINT.
Cold and hot are not activated in neutral area; it
symmetrically includes an upper part (hot) and a lower part
(cold) respect to temperature SETPOINT.
dtF>dtn ÷ 0 °C
dtC>dtn ÷ 0 °C
0,0 °C
dUU
HUMIDIFICATION differential
referred to main SETPOINT.
It is expressed in absolute value and defines the
humidification hysteresis referred to humidity SETPOINT.
(dUn+1) ÷ 10
rH%
5 rH%
dUd
DEHUMIDIFICATION differential
referred to humidity
SETPOINT. It is expressed in absolute value and defines the
dehumidification hysteresis referred to humidity SETPOINT.
(dUn+1) ÷ 10
rH%
5 rH%
dUn
NEUTRAL humidity area
referred to main SETPOINT.
Humidification and dehumidification are not activated in
neutral area; it symmetrically includes an upper part
(humidification) and a lower part (dehumidification) respect
to humidity SETPOINT.
dUU>dUn ÷ 0
rH%
dUd>dUn ÷ 0
rH%
0 rH%
d4
Defrosting interval
(hours). d4=0 disables defrosting
0 ÷ 24 hours
0 hours
d5
Defrosting maximum duration
(minutes)
1 ÷ 60 min
10 min
d6
End defrosting setpoint
.
Defrosting is not carried out if the temperature read by the
defrosting probe is higher than value
d6.
(In case of faulty probe, timed defrosting is carried out)
-35 ÷ 45 °C
15°C
d7
Dripping duration
(minutes)
At the end of defrosting, the compressor and the fans remain
still for the
d7
set time, the defrosting icon flashes.
0 ÷ 10 min
0 min
CHAP. 5 - Data programming
5.7