Peco TB158 Installation Instructions Download Page 1

h

READ THESE INSTRUCTIONS CAREFULLY BEFORE 
ATTEMPTING TO INSTALL, OPERATE OR SERVICE 
THIS THERMOSTAT. 

h

Failure to observe safety information and comply with 
instructions could result in PERSONAL INJURY, DEATH 
AND/OR PROPERTY DAMAGE.

h

To avoid electrical shock or damage to equipment, 
disconnect power before installing or servicing.

h

To avoid potential fire and/ or explosion do not use in 
potentially flammable or explosive atmospheres.

h

Retain these instructions for future reference.   This 
product, when installed, will be part of an engineered 
system whose specifications and performance 
characteristics are not designed or controlled by PECO.   
You must review your application and national and local 
codes to assure that your installation will be functional and 
safe.

WARNING

h

Use copper wire only, insulate or wire nut all un-used 
leads.

h

Care should be used to avoid electrostatic discharge to 
the microprocessor. 

h

This unit has configuration jumpers.   You may need to re-
configure this thermostat for your application. 
See page 2.

© COPYRIGHT 2005 PECO, INC. ALL RIGHTS RESERVED                                                                                 P/N 68838 3220-1472  Rev 0    Page 1

INSTALLATION INSTRUCTIONS

1. Install the T158 with the two furnished mounting screws to a 
standard 4-11/16" x 2-1/8" square device box with a 2" x 4" 
adapter ring.
2. For wall installations, mount the thermostat on an inside wall 
approximately 5 feet above the floor.   The location should 
provide circulation at average room temperature.   Avoid direct 
sunlight or sources of hot or cold air in the room or wall.
3. Remove the cover.   Mount thermostat base assembly to the 
outlet box using the screws provided, tighten the screws evenly 
but do not over tighten.   Connect wires as shown in the 
appropriate wiring diagram for your thermostat style.
4. To use a remote sensor on units with local sensing capability, 
remove jumper JP-1 to disable local sensing.   Failure to remove 
JP-1 will cause improper operation of the thermostat.
5. Remove the LCD plastic protective film. Reinstall the cover 
assembly.   Install the cover locking screw provided in the hole at 
the left side of   the control enclosure to complete the installation.
6. Checkout:   After wiring and installation are complete, energize 
the system and check the operation.   Adjust the thermostat as 
necessary to complete at least one cycle.   Be sure the 
thermostat and all other equipment are functioning correctly.

TB158

 

MICROPROCESSOR THERMOSTAT

On/Off and 3-Wire Controller

CAUTION

 

L

O

W

 V

O

L

T

A

G

E

C

O

N

N

E

C

T

IO

N

S

L

IN

E

 V

O

L

T

A

G

E

C

O

N

N

E

C

T

IO

N

S

WIRING DIAGRAM FOR ON/OFF OUTPUT

CONFIGURATION

WIRING DIAGRAM FOR 3-WIRE VALVE

CONFIGURATION

L

O

W

 V

O

L

T

A

G

E

C

O

N

N

E

C

T

IO

N

S

L

IN

E

 V

O

L

T

A

G

E

C

O

N

N

E

C

T

IO

N

S

L1 (HOT)

LO 

MED 

FAN

L2 OR NEUTRAL

24 VAC 1

24 VAC 2

SETBACK INPUT 

MAIN 1 OPEN

SEC 1 OPEN

MAIN 2 CLOSE

SEC 2 CLOSE

REMOTE PROBE

PIPE SENSOR

L1 (HOT)

LO

MED 

HIGH 

OR SINGLE SPEED FAN

24 VAC 1  

24 VAC 2 

SETBACK INPUT

FAN  

REMOTE PROBE

PIPE SENSOR

FAN

L2 OR NEUTRAL

24 VAC
XFMR

24 VAC
XFMR

MAIN 1

SEC 1

HEAT 2

MAIN

SECONDARY

OUTSIDE AIR

DAMPER OUTPUT

MAIN 1

OUTPUT

SECONDARY

 1 OUTPUT

DEMAND

OUTPUT

2ND STAGE

HEAT

OUTSIDE AIR

DAMPER OUTPUT

VOLTAGE

RATING

FAN AND SYSTEM SWITCHES

INDUCTIVE

FLA

LRA

RESISTIVE

AMPS

PILOT

DUTY

THERMOSTATIC

SWITCHING

(Pilot Duty)

24 VAC

NA

NA

NA

24 VA

10 VA

120 VAC

5.8

34.8

6.0

125 VA

N.A.

240 VAC

2.9

17.4

5.0

125 VA

N.A.

277 VAC

2.4

14.4

4.2

125 VA

N.A.

10

11

12

13

14

15

16

17

10

11

12

13

14

15

16

17

1

2

3

4

5

6

7

1

2

3

4

5

6

7

HIGH 

OR SINGLE SPEED FAN

Reviews: