3. Reader Connection
2. Mounting Controller
6. Locking Relay
5. Input B / REX Connection
4. Input A / DPS Connection
1. Package Contents
Diode (1)
Battery Leads (1)
Can Lock (1)
Jumpers (2)
Transformer (1)
14 VDC, 2 Amp
Red Cloud Node
Controller (1)
Enclosure Screws (2)
BAT
POWER
HEART
LINK
RELAY
OSDP
BUS
+
-
+ -
0 1 L
A
-
B
NC NO
C
12-24VDC
Mounting
-
Mount the enclosure securely to a wall.
A
Reader
-
The reader is mounted at the door with a 22/5 or 22/6 wire running
to the door controller. Wire the reader to the controller as shown above. Be
sure to check the polarity and voltage prior to powering the controller.
B
OSDP
-
Place jumper to enable OSDP (see OSDP reference guide at the end
of this guide for more info)
C
Piezo
-
Can be connected to available relay and configured with software.
BAT
POWER
HEART
LINK
RELAY
OSDP
BUS
+
-
+ -
0 1 L
A
-
B
NC NO
C
12-24VDC
+ -
0 1 L
A
-
B
NC NO
C
12-24VDC
A
Reader
ETHERNET
ACTIVITY
BAT
POWER
HEART
LINK
RELAY
OSDP
BUS
+
-
+ -
0 1 L
A
-
B
NC NO
C
12-24VDC
Red 1 Controller
OSDP
B
OSDP
Wiring
+ -
0 1 L
C
B
A
DPS Contact
A
-
B
Double
DPS Contact
A
DPS (Door Position Sensor)
- The DPS is mounted on the door frame with a
22/2 wire running from the DPS to the
controller
. Wire the DPS to the
controller
as shown above. For reporting double doors, wire the two-door
position in series and connect to the controller.
AUX Input
- A software rule can be programmed to trigger events or
outputs based on input triggers.
B
BAT
BUS
+
-
+ -
0 1 L
A
-
B
NC NO
C
12-24VDC
If using a powered REX,
run to any 12VDC
output on controller.
B
REX
D
A
Maglock
BUS
+
-
C
Maglock
- When installing a Maglock, it is typical to install a REX (request to
exit) at the door for free egress. Run an 18/2 wire from the maglock to the
controller
and REX as shown.
REX (Request to Exit)
- The REX is mounted at your desired location with an
18/5 wire. Wire the REX to the controller and maglock, as shown above. If
reporting is not needed in the system, simply eliminate the green input wire.
A
B
Jumper Block
- Use to designated (+) or (-) board voltage out of NO and NC.
If the jumper is off, the relay is a standard dry contact requiring an input into
C on the relay.
C
D
AUX Input
- A software rule can be programmed to trigger events or outputs
based on input triggers.
D
BUS
+
-
C
A
B
OR
Diode
- The provided diode must be installed when using a strike. Install at
the strike with the gray stripe on positive and black on negative.
A
NC
- Used for maglocks (or strikes in fail-safe configuration). Connect the
negative (-) of the maglock or strike to NC on the controller.
B
NO
- Used for strikes in fail-secure configuration. Connect the negative (-) of
the strike to NO on the controller.
C
Jumper Block
- Use to designate (+) or (-) board voltage out of NO and NC. If
the jumper is off, the relay is a standard dry contact requiring an input into C
on the relay.
D