7-Inch Local Display
Cntl Nr: PM375107-002
39
Device addresses are fixed in the Local Display. Addressing is set up for (1) end feed and (15) Tap Off
Boxes per bus run.
If device is not present or not monitored with BCMS at an address, that device should be disabled in
System View. For example, if you do not monitor end feeds, you should disable all end feeds for viewing in
System View. The Local Display will raise a communications alarm if a device is not monitored, but you
have selected it for display in System View.
4.7
Device Configuration: Setting Up Device Screens
You can modify the monitoring parameters for each device (end feed or Tap Off Box) by displaying its
device data screen, then linking to the device’s configuration page.
On the lower right of each device
screen, touch the
End Feed Config
(Figure 31) or
Tap Off Config
(Figure 32). Changing device
parameters makes changes to the device’s points list.
Note:
For Voltage Options and Current Options, Source 2 is not used.
Figure 31 End Feed Configuration Screen
Green boxes: Touch cell to toggle a value.
Red box:
Touch a
value to
change it; a
numeric
keypad
appears.