7-Inch Local Display
Cntl Nr: PM375107-002
33
6.
Press OK on Change Active Controller box.
7.
Press OK on Project Must Restart.
8.
Press Reset button on bottom left of the Local Display enclosure.
9.
Wait for Local Display to reboot.
Table 1 Modbus Settings
4.4
Modbus Addresses with Local Display
When using the 7" Local Display, Modbus addresses are predetermined for the bus runs connected to the
Local Display. Six (6) bus runs can be connected downstream from a single Local Display. When assigning
Modbus addresses for these bus runs, you must use the predetermined addresses, which are given on the
Setup
Screen and listed in Table 2 below:
M
ODBUS
M
ODE
V
IA
RS422
V
IA
E
THERNET
Settings
-
Communication Mode
Serial
Serial
-
Default Station
1
1
-
Modbus Protocol
RTU
RTU
-
32bit Work Mapping
Motorola
Motorola
-
Addressing
Decimal
Decimal
-
Start Address
1-based
1-based
-
Max Block Size (words)
16
16
-
Force Function Code 0x10
Disabled
Disabled
-
String Swap
Disabled
Disabled
-
Silent Time (ms)
1
1
-
Clock Register
0
0
-
Serial
-
Port
Com2
Com2
-
Baud
9600
9600
-
Parity
Even
Even
-
Data bits
8
8
-
Stop bits
1
1
Advanced
-
Enable Unicode
False
False
-
Byte Order
Intel
Intel
-
Timeout
400
400
-
Retries
3
3
-
Offline station retry time
10
10
-
Hide Comm. Error
False
False
-
Command Line Option
Routing
-
Communication
Serial
TCP
-
Mode
Transparent
Transparent
-
Timeout
5s
5s
-
Serial Port
Com4
Com4
-
Baud
9600
9600
-
Parity
Even
Even
-
Data bits
8
8
-
Stop bits
1
1
-
Ethernet Port
502
502