DPT-4001
Differential Pressure Transducer
Operation & Maintenance Manual
Engineered for accuracy, applicability,
durability and simplicity
Page 1: ...DPT 4001 Differential Pressure Transducer Operation Maintenance Manual Engineered for accuracy applicability durability and simplicity...
Page 2: ......
Page 3: ...LE OF CONTENTS TABLE OF CONTENTS i 1 INTRODUCTION 1 1 1 DESCRIPTION 1 1 1 1 Field Connections Output Load Limitations 1 1 1 2 Dimensions 2 2 CALIBRATION 3 2 1 UNIPOLAR ZERO CALIBRATION 3 2 2 BIPOLAR Z...
Page 4: ...essed electronically into an output signal linear to the differential pressure The DPT 4001 can be configured as a Unipolar device positive differential pressure only or a Bipolar device positive and...
Page 5: ...2 Revision Level 002 1 1 2 Dimensions Mount with 8 screws or 35mm Din Rail SPAN ZERO LO HI PCI INCORPORATED CONTROLS PARAGON TAG NO W O 1300 1234 POWER 12 36VDC OUTPUT 4 20mA RANGE 0 0 25 W C MODEL D...
Page 6: ...eiver Step 2 Apply power to the DPT Step 3 Identify ZERO potentiometer Step 4 With no pressure applied adjust the ZERO potentiometer for a reading of 4 01mA 2 2 BIPOLAR ZERO CALIBRATION The following...
Page 7: ...g 1 Verify Power Supply voltage is correct 2 Verify correct wire connections 3 Verify correct pressure connections 4 Verify input pressure differential with a manometer 5 Contact Factory Service Depar...
Page 8: ...Paragon Controls Incorporated P O Box 99 Forestville CA 95436 http www paragoncontrols com Phone 707 579 1424 Revision Level 002...