Payne PA1R Series Installation, Start-Up And Service Instructions Manual Download Page 1

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . .

1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23

I. Step 1 — Provide Unit Support

. . . . . . . . . . . . .

1

II. Step 2 — Field Fabricate Ductwork

. . . . . . . . . .

2

III. Step 3 — Install External Trap for

Condensate Drain

. . . . . . . . . . . . . . . . . . . . . . . . .

2

IV. Step 4 — Rig and Place Unit

. . . . . . . . . . . . . . .

2

V. Step 5 — Make Electrical Connections

. . . . . . .

7

VI. Step 6 — Make Outdoor-Air Adjustments

and Install Outdoor-Air Hood

. . . . . . . . . . . . . . .

9

VII. Step 7 — Adjust Evaporator-Fan Speed

. . . . . . 15

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24,25

I. Unit Preparation

. . . . . . . . . . . . . . . . . . . . . . . . . . 24

II. Return-Air Filters

. . . . . . . . . . . . . . . . . . . . . . . . . 24

III. Compressor Mounting

. . . . . . . . . . . . . . . . . . . . . 24

IV. Internal Wiring

. . . . . . . . . . . . . . . . . . . . . . . . . . . 24

V. Refrigerant Service Ports

. . . . . . . . . . . . . . . . . . 24

VI. Compressor Rotation

. . . . . . . . . . . . . . . . . . . . . . 24

VII. Cooling

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

VIII. Safety Relief

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

IX. Ventilation (Continuous Fan)

. . . . . . . . . . . . . . . 24

X. Operating Sequence

. . . . . . . . . . . . . . . . . . . . . . 24

SERVICE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-28

I. Cleaning

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

II. Lubrication

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

III. Condenser-Fan Adjustment

. . . . . . . . . . . . . . . . 26

IV. Condenser Coil Grille

. . . . . . . . . . . . . . . . . . . . . 27

V. Refrigerant Charge

. . . . . . . . . . . . . . . . . . . . . . . . 27

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . . . . 29-31

START-UP CHECKLIST

. . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.

Untrained personnel can perform the basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe pre-
cautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguisher available for all brazing operations.

WARNING:

Before performing service or mainte-

nance operations on unit, turn off main power switch
to unit. Electrical shock could cause personal injury.

1. The power supply (volts, hertz, and phase) must corre-

spond to that specified on unit rating plate.

2. The electrical supply provided by the utility must be suf-

ficient to handle load imposed by this unit.

3. Identify locations of electrical inlets, condensate drain,

duct connections and required clearances before setting
unit in place.

4. This installation must conform with local building codes

and with NEC (National Electrical Code) or NFPA
(National Fire Protection Association) 54 TIA-54-84-1.
Refer to Provincial and local plumbing or wastewater
codes and other applicable local codes.

5. Approved for outdoor installation on wood flooring or on

class A, B, or C roof covering materials.

INSTALLATION

Unit is shipped in the vertical configuration. To convert to
horizontal configuration, remove screws from side duct open-
ing covers and remove covers. Using the same screws, install
covers on vertical duct openings with the insulation-side down.
Seals around duct openings must be tight. See Fig. 1.

NOTE:

When installing any accessory item, see the man-

facturer’s

installation

instructions

packaged

with

the

accessory.

A qualified installer or agency must use only factory-authorized
kits or accessories when modifying this unit.

I. STEP 1 — PROVIDE UNIT SUPPORT

A. Roof Curb

Assemble and install accessory roof curb in accordance with
instructions shipped with curb. See Fig. 2. Install insulation,
cant strips, roofing felt, and counter flashing as shown. Duct-
work must be attached to curb, not to the unit. 
If electric or
control power is to be routed through the basepan, attach the
accessory thru-the-bottom service connections to the base-
pan in accordance with the accessory installation instruc-
tions. Connections must be installed before unit is set on roof
curb.

IMPORTANT:

The gasketing of the unit to the roof curb is

critical for a watertight seal. Install gasket supplied with the
roof curb. Improperly applied gasket can also result in air
leaks and poor unit performance.

Curb should be level. This is necessary for unit drain to func-
tion properly. Unit leveling tolerances are shown in Fig. 3.
Refer to Accessory Roof Curb Installation Instructions for ad-
ditional information as required.

B. Slab Mount (Horizontal Units Only)

Provide a level concrete slab that extends a minimum of 6 in.
beyond unit cabinet. Install a gravel apron in front of con-
denser coil air inlet to prevent grass and foliage from
obstructing airflow.

NOTE:

Horizontal units may be installed on a roof curb if

required.

installation, start-up and
service instructions

SINGLE PACKAGE ROOFTOP
ELECTRIC HEATING/ELECTRIC COOLING UNITS

PA1R

Sizes 036-072

3 to 6 Tons

Cancels: New

II PA1R-36-1

2/15/98

Summary of Contents for PA1R Series

Page 1: ...orm with local building codes and with NEC National Electrical Code or NFPA National Fire Protection Association 54 TIA 54 84 1 Refer to Provincial and local plumbing or wastewater codes and other app...

Page 2: ...connections either drain connection can be used with vertical or horizontal applications When using the standard side drain connection make sure the plug in the alternate bottom connection is tight b...

Page 3: ...1 29 NPT CRBTMPWR002A00 THRU THE BOTTOM ROOF CURB ACCESSORY A UNIT SIZE PA1R CRRFCURB001A00 18 29 356 036 072 Fig 2 Roof Curb Dimensions NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated...

Page 4: ...es through holes in base rail as shown in detail A Holes in base rails are centered around the unit cen ter of gravity Use wooden top skid when rigging to prevent rig ging straps from damaging unit 3...

Page 5: ...earance is optional c Overhead 60 in to assure proper condenser fan operation d Between units control box side 42 in per NEC National Electrical Code e Between unit and ungrounded surfaces control box...

Page 6: ...1 20 2 40 Alt 1 00 1 00 1 80 Motor Frame Size Std 48 48 48 56 Alt 48 48 56 Nominal Rpm High Low Std 860 800 1075 970 1075 970 Alt Fan Rpm Range Std 1070 1460 Alt 760 1090 840 1185 900 1300 Motor Bear...

Page 7: ...tal is located adjacent to the corner post on the left side of the power wiring access panel B Field Power Supply All units except 208 230 v units are factory wired for the volt age shown on the namep...

Page 8: ...power wiring access panel See Fig 8 Connect control wires to the low voltage connections located inside low voltage access panel See Fig 10 and 11 The barrier provides the UL Underwriters Laboratorie...

Page 9: ...re top of hood with the 4 screws removed in Step 3 See Fig 14 LEGEND AHA Adjustable Heat Anticipator CC Cooling Compensator TC Thermostat Cooling TH Thermostat Heating Field Wiring Factory Wiring NOTE...

Page 10: ...8 38 6 0 7 2 10 6 15 10 38 8 8 10 6 14 9 15 14 38 11 5 13 8 18 9 20 17 38 14 0 16 8 22 7 25 21 38 Alt 2 1 9 3 15 9 41 6 0 7 2 11 6 15 10 41 8 8 10 6 15 9 20 15 41 11 5 13 8 19 9 20 18 41 14 0 16 8 23...

Page 11: ...36 1 45 45 35 35 191 191 7 9 10 5 21 9 25 3 36 1 38 1 45 45 35 35 191 191 12 0 16 0 33 4 38 4 48 2 54 6 50 60 44 50 191 191 15 8 21 0 43 8 50 5 61 2 69 6 70 70 56 64 191 191 19 9 26 5 55 2 63 8 75 6 8...

Page 12: ...er access panel Remove outdoor air opening panel Save panels and screws See Fig 16 Remove optional outdoor air damper hood package from filter section 3 Assemble outdoor air hood top and side plates a...

Page 13: ...ee Fig 22 Set for 3 F below indoor room thermostat set ting If accessory enthalpy control EC is used in place of OAT see instructions shipped with EC for installa tion and adjustment See Fig 22 11 Con...

Page 14: ...ing 5 in Fig 21 Durablade Economizer Minimum Position Setting MINIMUM POSITIO N OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I D I T Y 90 70 60 30 10 D C B A 60 65 70 75 55 50 85...

Page 15: ...ange setscrew see Fig 26 4 Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed Increas ing fan speed increases load on motor Do not exceed maxi mum...

Page 16: ...Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure Unit warranty will not be affected Single phase motor 3 phase motor Table 5...

Page 17: ...ors up to the wattage rat ings shown will not result in nuisance tripping or premature motor failure Unit warranty will not be affected For additional information on motor performance refer to Table 4...

Page 18: ...confidence Using your fan motors up to the wattage rat ings shown will not result in nuisance tripping or premature motor failure Unit warranty will not be affected For additional information on moto...

Page 19: ...range 900 to 1300 rpm All other rpms require field supplied drive 7 To convert watts to bhp watts input x motor efficiency bhp 746 Motor efficiency 74 Table 11 Fan Performance PA1R072 Vertical Discha...

Page 20: ...953 348 1000 570 109 627 149 738 189 800 259 848 288 895 308 936 348 977 388 1100 614 149 670 189 758 229 812 288 863 308 914 348 960 388 1005 428 1200 658 189 710 229 780 279 840 318 889 358 938 398...

Page 21: ...899 1600 642 315 699 378 755 447 811 515 913 672 957 751 1001 830 1080 971 1700 675 378 728 441 782 510 836 578 935 746 979 825 1023 904 1101 1053 1800 709 431 759 504 810 578 860 651 957 820 1001 904...

Page 22: ...7 756 1108 920 1186 1104 1263 1328 1343 1615 1431 1829 1600 693 327 754 388 867 531 963 664 1052 828 1130 991 1205 1175 1278 1380 1350 1645 1424 1921 1700 729 388 787 450 895 593 991 746 1075 899 1154...

Page 23: ...251 1517 1322 1700 1390 1901 1456 2102 1514 2300 1569 2487 2700 1109 1258 1140 1318 1212 1482 1283 1656 1352 1849 1418 2041 1483 2257 1543 2462 2800 1148 1396 1177 1456 1246 1621 1316 1805 1383 1997 1...

Page 24: ...ides pressure relief under abnormal tempera ture and pressure conditions IX VENTILATION Continuous Fan Set fan and system selector switches at ON and OFF posi tions respectively Evaporator fan operate...

Page 25: ...outlined above to reinstall the condenser fan grille and condenser fan top cover Two Row Coils size 072 see Fig 28 NOTE Save all screws removed in this section The screws must be used when reinstalli...

Page 26: ...e condenser fan assembly A Manual Outdoor Air Damper If outdoor air damper blade adjustment is required see Manual Outdoor Air Damper section on page 9 B Economizer Adjustment Refer to Durablade Econo...

Page 27: ...e required Connect the pres sure gage to the service port on the suction line Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not affe...

Page 28: ...Fig 34 Cooling Charging Chart PA1R060 Fig 35 Cooling Charging Chart PA1R072 Scroll 28...

Page 29: ...estriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Low refriger...

Page 30: ...and EC settings and the economizer control board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are functioning and wired pro...

Page 31: ...dard SW1 Switch Fully Open SW2 Switch Fully Closed SW3 Switch Min Vent Position SW4 Switch Max Vent Position TB Terminal Block TC Thermostat Cooling TDR Time Delay Relay TH Thermostat Heating TRAN Tra...

Page 32: ......

Page 33: ......

Page 34: ...lar video based formats and materials All include video and or slides plus companion book Classroom Service Training which includes hands on experience with the products in our labs that can mean incr...

Page 35: ......

Page 36: ...NSTALLATION INSTRUCTIONS CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS CHECK PULLEY ALIGNMENT AND BELT TENSION REFER TO INSTALLATION INSTRUCTIONS III START UP EL...