90% of installation faults are caused by wiring errors on the RS485 data line. 

Special attention to getting this right first time saves a lot of time and effort.

RS485 data line

The data line must be wired in a single daisy chain.  The data converter may be located anywhere along the data 

line.  20 ohm terminating resistors must be linked across each data pair at the beginning AND end of the line.  

This can be done on many units with a switch or jumpers.  If not, free resistors are provided with the converter.  

The example below requires terminating at the RS485 converter and also the 3rd ACU at the end.

Control unit installation

Wire the components to the Access Control Unit (ACU) as shown on the first page. This will include:

                 - Reader/Keypad

                 - Electric Lock

                 - Power supply

                 - Any other optional components

Press the exit button or in the absence of an exit button, short the 0V and exit terminals together. The lock relay 

LED will come on and the lock should release.

RS485 data line checks

PC Installation 

The current specification for compatible PC hardware, network and operating systems is available on our 

website at the following link:  

http://paxton.info/720

The reader’s default indication has all the LED’s on.  Access granted is denoted with a single flashing Green LED, 

Access Denied is a single flashing Red LED. 

Check the screen of the data cable is continuous - this provides the 0V DC system reference.

Check that there are no data line to screen shorts.

Check the resistance across each data pair is 60-80 ohms.

Power down all TCP/IP, USB and RS232 converters  (individual and Net2 plus). 

END OF LINE TERMINATION 

- 20 ohm resistors must be linked across each data 

pair at the beginning AND end of the data line.  This can be done on many units with 

a switch or jumpers.  If not, free resistors are provided with the converter. If the data 

converter is located at a point along the data line, termination will then be required in 

the two ACU’s at each end of the line.

READER & DATA CABLE SCREENS.

- Data cable screens and spare cores MUST be connected throughout.

- Reader and keypad screens where provided, should be connected to the Black 0V terminal. 

Summary of Contents for Ins-30000 Net2 classic

Page 1: ...EEN and RED wires go to reader terminals Reader keypad optional Tamper switch optional Door contact switch held closed by door For a fail open lock Maglock the 0V loop wire is connected to the N C terminal not the N O 27 01 2010 To 12V DC power supply BEFORE CONNECTING THE READER This product is not suitable for retail sale All warranties are invalid if this product is not installed by a competent...

Page 2: ...85 data line checks PC Installation The current specification for compatible PC hardware network and operating systems is available on our website at the following link http paxton info 720 The reader s default indication has all the LED s on Access granted is denoted with a single flashing Green LED Access Denied is a single flashing Red LED Check the screen of the data cable is continuous this p...

Page 3: ...s more than one Net2 operator to connect into the same Net2 system at any one Qtime Connections can be established over most TCP IP networks including VPN through the Internet Net2 QWorkstation software is included on the Net2 CD and is an option during installation No addition license is Qrequired Net2 Workstation software must be the same version as that running on the Net2 server QWorkstation s...

Page 4: ...ftware installation 10 000 10 000 250 64 50 1 2 2 2 1 200 1 50 2 454 11V DC 15V DC 110 mA 350 mA 24V DC 4 A 1 A 500 mA 0 C 55 C 103 mm 118 mm 23 mm Voltage Relay switchable current Relay switchable voltage Operating temperature Battery limits Electrical Environment Dimensions PCB Current depending on activity Features Waterproof Min Width Height Max Min Max Depth Min Max Number of PIN s Access Lev...

Reviews: