20
en
Maximum hot water set temperature
Main menu / Store loading / Set max
Adjustment channel Description
Adjustment range /
selection
Factory
setting
Set max
Maximum hot water set temperature
20 … 75 °C
60 °C
This parameter determines the maximum limitation for the adjustment of the hot
water set temperature T-HW set.
∆
Tmin
Main menu / Store loading /
∆
Tmin
Adjustment
channel
Description
Adjustment range /
selection
Factory
setting
∆
Tmin
Set temperature difference between between
source and sink
5 … 30 K
10 K
The parameter
∆
Tmin determines the set temperature difference, that has to be
reached between T-Source t. and T-Sink b., in order to activate store loading.
∆
T store
Main menu / Store loading /
∆
T store
Adjustment
channel
Description
Adjustment range /
selection
Factory
setting
∆
T store
Set difference between hot water set tempera-
ture and store temperature
1 … 10K
4 K
The parameter
∆
T store determines the set temperature difference, that has to
be reached between the temperature at T-Sink c. and the adjusted set tempera-
ture T-HW set, in order to activate store loading.
Sliding set value
Main menu / Store loading / Sliding set value
Adjustment channel Description
Adjustment range /
selection
Factory
setting
T-HW set sl.
Activation of the function
Yes, No
Yes
back
When the T-FL temperature measured at the T-FL sensor is insuffi cient for reaching
the T-HW set temperature, T-HW set will be decreased dynamically.
The speed of the primary pump will be controlled such that the dynamic set tem-
perature T-HW set sl. is held at the T-HW sensor .