Patol 5000 Series Manual Download Page 1

Page 1 of 15 

D1125  -  Issue 2  - 1  December 2009 

Series 5000 - Manual 5010 / 5020 

Patol Limited 

 

 

 

 5000 Series  

Infra-red Fire Detection System 

Internal Lens Cleansing & Purge Air Configuration 

5010 Sensor Head - 5020 Controller

 

 

 

SPECIFICATION  

INSTALLATION - COMMISSIONING 

OPERATION - MAINTENANCE 

 

 

 

 
 
 
 
 

 

Document Ref : D1125 

 

 

 

 
 
 

 

Issue 

Change 

Date 

Remarks 

Original 

25/05/05 

 

Additions 

01/12/09 

 

 

 

 

 

Patol Limited 

Rectory Road, 
Padworth Common, 
Berkshire.  RG7 4JD 
United Kingdom. 
Tel  :  +44 (0) 118 9701 701 
Fax :  +44 (0) 118 9701 700 
Email : [email protected] 
Web : www.patol.co.uk 

Summary of Contents for 5000 Series

Page 1: ...ir Configuration 5010 Sensor Head 5020 Controller SPECIFICATION INSTALLATION COMMISSIONING OPERATION MAINTENANCE Document Ref D1125 Issue Change Date Remarks 1 Original 25 05 05 2 Additions 01 12 09 P...

Page 2: ...ATION 3 1 Sensor Head 3 2 Controller Cable 3 3 Purge Air Supply 4 COMMISSIONING 4 1 Cable Checks 4 2 Controller Set Up 4 3 Power Up Procedure 4 4 Sensor Head Purge Air Supply 4 5 Hot Body Simulation T...

Page 3: ...c Detection of hazards at temperatures below flame point including both embers and buried hot spots Air purged system for Dusty environments with air pressure monitoring Eight high integrity detectors...

Page 4: ...plosive gas or dust is prevented The arrangement can permit the unit to be employed in a Hazardous Area depending on applicable local regulations The air purging is essential in dusty environments suc...

Page 5: ...prior to fittment of the module The housing has a high level of ingress protection IP67 The unit incorporates a user programmable DIL switch to set the options which include detector sensitivity sett...

Page 6: ...ush button Reset Push button Lamp Test Push button 2 4 9 Program DIL Switch 8 Pole Also refer to section 2 5 Sensitivity 4 level Latching Auto Reset Alarm One Shot Voting Trip One Shot Voting Auto Res...

Page 7: ...set delay is in effect the Scan Period within which a second channel must occur after first detection Poles 5 6 of the DIL switch set the delay Scan period 2 5 1 Detector Sensitivity The detection sen...

Page 8: ...fault monitored The above diagram shows how both opening and closing reporting contacts should be configured If the circuit is not utilised then the terminals should have a 10k resistor connected to...

Page 9: ...at an adjacent junction box Type 5040 and 5044 multistage blowers are shown below For type 5051 single stage units and other varieties within the range refer to separate datasheets As standard each b...

Page 10: ...ny interposing cable must maintain the screen shield connection On sites defined as Hazardous Areas it may be a requirement that all cables are installed in conduit In this case it is recommended that...

Page 11: ...he APB may need to be located in a Safe Area on sites with a Hazardous classification There are limits to the distance that any APB can deliver the required air to the Sensor which are principally dep...

Page 12: ...air delivery is insufficient to operate the switch then the Air Fault LED will be illuminated at stage 4 3 4 following Reference should be made to section 4 4 4 3 3 Apply the controller electrical su...

Page 13: ...sor module after removal of the two retaining screws 4 5 Hot Body Simulation Tests A heat simulation test should be conducted This testing may be facilitated by temporarily setting the system to auto...

Page 14: ...lay contact 5 4 Reset Latched Alarm and Trip conditions may be normalized by Operation of the Controller s integral Reset push button Operation of the remote reset push button signal if implemented 5...

Page 15: ...IR emitting target into the view field of the Sensor Head and checking the consequential Alarm Trip operation The controller may be temporarily set for auto reset mode by means of the DIL switch The...