4.8. Contact Input Detection
It detects the status change of the contact input and perform the set-up process.
The setup for the contact input detection is done in the Web Setup.
①
Set the action to be executed when the setting input status 1 to 4 changes.
②
Press the "Set" button to apply the settings.
MEMO
Only when the command control method is selected, the operation screen is displayed during
contact input.
The contents that operates for each contact input can be selected.
Select
Operation
Operation Contents
Available Modes
No Operation Even if contact input is turned ON/OFF, it will not operate.
-
Clear
When the contact input is turned ON, clearing is executed.
Nothing will operate when it is OFF.
Signal Tower Mode
Smart Mode
(Single Display, Time Trigger, Pulse Trigger)
Mute
While the contact input is turned on, Mute is ON.
While the contact input is turned off, Mute is OFF.
Smart Mode
(Single Display, Time Trigger, Pulse Trigger)
STOP
While the contact input is turned on, STOP is turned ON.
While the contact input is turned off, STOP is OFF.
Smart Mode
(Time Trigger, Pulse Trigger)
Pulse Trigger
While the contact input is turned on, the Pulse Trigger is
turned ON.
Nothing will operate when it is OFF.
Smart Mode
(Pulse Trigger)
[Table of Available Modes]
Signal Tower
Mode
Smart Mode
Single Display
Time Trigger
Pulse Trigger
Operation
Clear
OK
OK
OK
OK
Mute
No
OK
OK
OK
STOP
No
No
OK
OK
Pulse Trigger
No
No
No
OK
MEMO
• When it is not in an available mode, even if the contacts operate, it won't operate.
• The Mute and STOP can only be controlled in Smart Mode.