Wiring Diagram
IN195-3
12
Wiring diagram
Speed Controller Instructions
For models CONTRE3-A and CONTRE6-A
Technical Data
Code
Current Range
Fuse
CONTRE3-A (STL-0-30-AT)
0.1-3.0A
5.0A
CONTRE6-A (STL-0-60-AT)
0.5-6.0A
10.0A
Enclosure: Plastic R-ABS, UL94-VO, grey RAL 7035, IP54
Max ambient temperature: 35degrees centigrade
For indoor use only, non-condensing
The electronic speed controller of these series control the speed of single phase (230 VAC – 50
HZ) voltage controllable motors by varying the supplied voltage through phase angle control.
There is a potentiometer and a separate ON/OFF switch with built in tell tale, The minimum
speed allowed can be adjusted internally with a little trimmer (Factory pre-set = 100V). The
terminal board has a supplementary connection to bypass the ON/OFF switch (automatic start)
or to branch off230V not controlled (three wire motor connection, valve, lamp, damper, etc...)
There are two working modes internally selectable by placing or removing the red jumper on
the PCB (See illustration)
Kickstart : the motor will always start (or reset ) at max speed for 8 seconds, after that the
motor speed automatically follows the position of the potentiometer.
Normal start : the motor starts according to the position of the potentiometer.
1.
Be sure that the controller is in the OFF position.
2.
Take off the box cover by loosening the 4 screws. Note that the potentiometer is
connected to the PCB with 2 wires.
3.
Connect mains, motor(s) and earth cables of the proper diameter to the terminals
according to the scheme below.
4.
Start the controller and adjust the little trimmer so that the motor continues turning or
restarts smoothly in case of power faults. The minimum speed is factory preset at 100V
5.
Close the box and verify that the installation works fine.
6.
The operating position must be shown below.
Connections
LN
Mains supply 230Vac-50Hz
N
neutral
Pe
earth connection
L1N
230Vac not regulated output for connecting lamp, valve, dampers … or
three wire motor connections; branched off after switch and fuse
Input: to bypass switch and fuse (ATTENTION)
N
regulated output to motor
Jumper
Jumper removed = normal working mode
Jumper in place = kickstart working mode
Trimmer
minimum speed adjustment trimmer