PARKER Accumulator & Cooler Division 

15102 Sommermeyer, Suite 125, Houston, Texas, 77041     Tel. (713) 937-8900  Fax: (713) 937-0438 

Installation and Servicing Instructions: 
ULDC Air/Oil Cooler 

These instructions should be observed prior to installation of 
the PARKER ULDC cooler. 

Mounting 

The PARKER coolers permit both horizontal and vertical 
mounting. The conduit entry of the DC motor must always be 
turned downwards.  To prevent personal injury, always secure 
the cooler adequately.  The distance from the nearest 
obstruction should not exceed half the height of the cooler 
core. 

Hydraulic connection

 

Connect the cooler as illustrated below using hydraulic hoses 
both to and from the cooler.  We recommend mounting in a 
separate cooling circuit when possible.  When this can not be 
done, install the cooler in the system return line.  Avoid 
linking to systems that could cause pressure spikes in excess 
of 200 psi.  PARKER shall not be held responsible for any 
consequences due to modification and/or variation with regard 
to connections. 

Electrical Connection

 

PARKER ULDC cooler is supplied with a 12V or 24V DC 
motor.  Connect the power source to the cooler as illustrated 
below.  For protection of the motor, always use a relay.  

The circuit diagram below should be applied when connecting 
a cooler equipped with a switch box. 

In case where the cooler is provided with a thermoswitch, use 
a relay if the current lULDC is greater than: 
10 A 

at 

12V DC 

5 A 

at 

24V DC 

Prior to Start-Up 

Check cooler core and fan guard for damage.

Check that the cooler is provided with a caution label for
fan rotation

Check that the cooler is correctly connected according to
the above.  PARKER shall not be held responsible for any
consequences due to variations.