Bulletin 100-50-9.1 –
Page 127
12. Press the
SET
button to move the valve to the desired
position. The display will revert to
.
13. Repeat steps 9 – 12 to move the valve to any desired
position.
14. When finished, press the
ESC
button twice to return to
the
default
display and exit
Test
Mode
.
19.12 MANUALLY POSITION EEPR
1. From the
default
display, press the
button. The
display will show
.
2. Use the
▲▼
buttons to enter the Technician password
and press
SET.
3. The display will show
.
4. Press the
▼
button until
e
is displayed.
5. Press
SET
to enter the Test sub-menu. The display will
show
e
(Test Enable).
6. Press
SET
to enter ON/OFF sub-menu. The display will
show
o
(Or current state of
Test
Enable
).
7. Press the
▲
button to
o
.
8. Press
SET
to activate
Test Mode.
The display will
revert to
e
.
9. Press the
▲
button until
is displayed.
10. Press the
SET
button. The current EEPR % open value
will be displayed.
11. Use the
▲▼
buttons to adjust the desired valve
position.
12. Press the
SET
button to move the valve to the desired
position. The display will revert to
.
13. Repeat steps 9 – 12 to move the valve to any desired
position.
14. When finished, press the
ESC
button twice to return to
the
default
display and exit
Test Mode.
19.13 CLEAN MODE
The S3C Case Control supports a Clean Mode. Putting the
control in this state shuts off refrigeration and evaporator
fans, suspends defrost requests and disables all alarms. They
will remain off until the user terminates the Clean Mode.
This allows for either cleaning of the case or performing
service functions that require the case to be in an “OFF”
state. Clean Mode can be initiated or terminated using any
S3C Display Module (DM) in the case line-up.
Warning:
The Clean Mode feature is not to be used
for safety critical servicing. Use proper lockout tag out
producers, as defined by local requirements and codes, on
the case if electrical repair or other safety critical servicing
is required.
19.13.1 SINGLE KEY PRESS CLEAN MODE
ENTRY
Warning:
It is imperative that Clean Mode be manually
terminated in a timely fashion to prevent product loss or
possible equipment malfunction. Single key press Clean
Mode entry:
1. From the
default
display, press and hold the
and
▼
buttons for 3 seconds. The display will show
.
2. Use the
▲▼
buttons to enter the Technician password
and press
SET.
3. The display will show
.
4. Press
SET
to enter ON/OFF sub-menu. The display will
show
o
(Or current state of Clean Mode).
5. Press the
▲
button to
o
.
6. Press
SET
to activate
Clean Mode.
19.13.2 STANDARD MENU ENTRY FOR
CLEAN MODE
1. From the
default
display, press the
button. The
display will show
.
2. Use the
▲▼
buttons to enter the
service
password and
press
SET.
3. The display will show
.
4. Press
SET
to enter ON/OFF sub-menu. The display will
show
o
(Or current state of Clean Mode).
5. Press the
▲
button to
o
.
6. Press
SET
to activate
Clean Mode.
19.13.3 TO EXIT CLEAN MODE AND RESUME
NORMAL OPERATION
1. From the
default
or
display, press the
button.
The display will show
.
2. Use the
▲▼
buttons to enter the
Technician
password
and press
SET.
3. The display will show
.
4. Press
SET
to enter ON/OFF sub-menu. The display will
show
o
(Or current state of Clean Mode).
5. Press the
▲
button to
o
.
6. Press
SET
to deactivate
Clean Mode.
19.14 TEST MODE
The controller may be placed in test mode to manually
toggle the internal relays or operate the step motor
valves. This mode can help verify correct operation of the
components and may aid in troubleshooting.
Note: Once
the controller is placed in test mode (
N
set to
o
),
the controller will remain in test mode until
N
is set
to
off
or by pressing the ESC button until the default
display (case temperature) is shown.