Page 126
– Bulletin 100-50-9.1
3. Press
SET
button to show EEV position.
4. Press
ESC
button three times to return to
default
display.
19.7.2 MULTI-COIL CASE
For Coil 1:
1. From the
default
display, press the
▲
button to
then press
SET.
2. Press the
▲
button and scroll to
1
.
3. Press
SET
button to show EEV position.
4. Press
ESC
button three times to return to
default
display.
For Coil 2:
1. From the
default
display, press the
▲
button to
2
then press
SET.
2. Press the
▲
button and scroll to
.
3. Press
SET
button to show EEV position.
4. Press
ESC
button three times to return to
default
display.
For Coil 3:
1. From the
default
display, press the
▲
button to
3
then press
SET.
2. Press the
▲
button and scroll to
.
3. Press
SET
button to show EEV position.
4. Press
ESC
button three times to return to
default
display.
19.8 VIEW EEPR POSITION
19.8.1 LINE-UP EEPR
The EEPR position may be viewed from any Display Module
(DM) on the line-up.
1. From the
default
display, press the
▼
button to show
N
then press
SET.
2. Press the
▲
button and scroll to
.
3. Press
SET
button to show EEPR position.
4. Press
ESC
button three times to return to
default
display (discharge air).
19.8.2 CASE EEPR
Each case EEPR position can only be viewed thru the
corresponding case Display Module (DM).
1. From the
default
display, press the
▼
button to show
then press
SET.
2. Press the
▲
button and scroll to
.
19.9 ADJUST SUPERHEAT SETPOINT
1. From the
default
display, press the
button. The
display will show
.
2. Use the
▲▼
buttons to enter the Technician password
and press
SET.
3. The display will show
.
4. Press the
▼
button until
is displayed; press
SET.
5. Use the
▲▼
buttons and scroll to
e
; press
SET.
6. Press the
▲
button to scroll to
(basic menu); press
SET.
7. Press the
▲
button to scroll to
h
(superheat
setpoint); press
SET.
8. Use the
▲▼
buttons to increase or decrease setpoint;
press
SET
to make the change.
9. To exit and discard changes, press
ESC
button four
times to return to
default
display.
Note: Settings that are changed under the Service access will
be discarded once exiting to the default display. For permanent
changes, enter the menu using Administrator password.
19.10 ADJUST DISCHARGE AIR SETPOINT
1. From the
default
display, press the
button. The
display will show
.
2. Use the
▲▼
buttons to enter the Technician password
and press
SET.
3. The display will show
.
4. Press the
▼
button until
is displayed; press
SET.
5. Use the
▲▼
buttons and scroll to
e
; press
SET.
6. Press the
▲
button to scroll to
(basic menu); press
SET.
7. Press the
▲
button to scroll to
d
(discharge air
setpoint); press
SET.
8. Use the
▲▼
buttons to increase or decrease setpoint;
press
SET
to make the change.
9. To exit and discard changes, press
ESC
button four
times to return to
default
display.
19.11 MANUALLY POSITION EEV
1. From the
default
display, press the
button. The
display will show
.
2. Use the
▲▼
buttons to enter the Technician password
and press
SET.
3. The display will show
.
4. Press the
▼
button until
e
is displayed.
5. Press
SET
to enter the Test sub-menu. The display will
show
e
(Test Enable).
6. Press
SET
to enter ON/OFF sub-menu. The display will
show
o
(Or current state of
Test Enable
).
7. Press the
▲
button to
o
.
8. Press
SET
to activate
Test Mode
. The display will
revert to
e
.
9. Press the
▲
button until
is displayed.
Note: for
multiple coil cases
1
,
2
,
3
may be
shown.
10. Press the
SET
button. The current EEV % open value
will be displayed.
11. Use the
▲▼
buttons to adjust the desired valve
position.