Bulletin 100-50-9.1 –
Page 11
Data Interface (3)
1. RS-485 MODBUS, BACnet MSTP (Building Automation
System)
2. Ethernet MODBUS, BACnet/IP (Case Control to Case
Control or Building Automation System)
Notes:
1. One Ethernet port can be used to connect case
controller to case controller and the second
port can be connected to the BAS.
2. Both Ethernet Ports can be used for case con-
troller to case controller and the RS-485 can be
used from the case controller network to the
BAS.
Environmental
Operating
Temperature 0°C (32°F)- +50°C(122°F)
Humidity 10% - 95% RH non condensing
Storage
Temperature -25°C (-13°F)- +70°C(158°F)
Humidity 10% - 90% RH non condensing
Compliance
UL 60730-1 & CAN/CSA-E60730-1:13
UL 60730-2-9 & CAN/CSA-E60730-2-9:15
RoHS, 2011/65/EU
FCC Title 47, Chapter I, Subchapter A, part 15, Class A
Digital Device
CAN ICES-3 (A)/NMB-3(A)
3.2
S3C VALVE MODULE
Electrical
Supply 22 - 26 VDC @ 0.75A minimum
Notes:
1. External DC Power Supply must be Class 2 and
Class II rated.
2. Maximum wire length between power supply
and Valve Module is 400 ft. (22AWG minimum)
Analog Inputs (7)
Temperature Inputs (6)
10K Thermistor (Software selectable 2K, 3K)
Pressure Transducer (1)
.5 – 4.5 VDC Ratiometric output.
Pressure ranges: 150 PSI, 300 PSI, 500 PSI, 652 PSI and
Custom
(Absolute or Gauge software selectable)
Relay Outputs (1)
Solenoid/Pulse EEV – 240VAC/1A
Stepper Motor (2)
Unipolar/Bipolar 13.5VDC @ 400mA/Ø
200 pps/400 pps Software selectable
Data Interface (1)
RS-485 (Not Used)
Environmental
Operating
Temperature 0°(32°F)- +50°C(122°F)
Humidity 10% - 95% RH non condensing
Storage
Temperature -25°C (-13°F)- +70°C(158°F)
Humidity 10% -90% RH non condensing
Compliance
UL 60730-1 & CAN/CSA-E60730-1:13
UL 60730-2-9 & CAN/CSA-E60730-2-9:15
RoHS, 2011/65/EU
FCC Title 47, Chapter I, Subchapter A, part 15, Class A
Digital Device
CAN ICES-3 (A)/NMB-3(A)
3.3
S3C DISPLAY MODULE
Electrical
Supply 22 - 26 VDC @ 0.5A minimum
Notes:
1. External DC Power Supply must be Class 2 and
Class II rated.
2. Maximum wire length between power supply
and Display Module is 400 ft. (22AWG minimum)
Environmental
Operating
Temperature 0°C - +50°C
Humidity 10% - 95% RH non condensing
Storage
Temperature -25°C - +70°C
Humidity 10% - 90% RH non condensing