14
4 Installation and Safety instructions
•
The converter must be mounted vertically with the power block above using an omega
guide.
•
A space of at least 100 mm. must be left free above and beneath the converter.
•
Make sure that the converter is sized properly for the motor it will be used with.
Compare the rated voltages and currents.
•
Connect the cabinet/converter/motor in accordance with the instructions that are given
in this section, with the regulations for electromagnetic compatibility and with the
safety regulations that are in force.
•
The user is responsible for the protection fuses in the AC power supply of the
converter.
•
Power and control cables must be kept separate (min. 20cm) and, if crossing is
necessary, it should be right-angled. The motor cables and the power cables can never
be parallel.
•
All power cables must have a sufficient section (see the table given in paragraph 2.7)
and must conform to the IEC227-2 regulation.
•
The cables connected to the converter at the terminal cannot be consolidated with tin-
lead welding (EN60065, Art.15.3.5).
•
Make sure that the converter and the motor are correctly grounded.
•
Make sure the maximum power at terminals L1, L2, and L3 does not exceed by more
than 10% the rated voltage even in the worst case (see EN60204-1, section 4.3.1).
Excessive supply voltage can damage the converter.
•
Do not ever remove the electrical connections from a live converter.
•
Follow carefully the instructions given in this manual step by step during the
installation. If you have questions or problems, contact our customer assistance
service.
•
After power supply has been disconnected and the converter has been off for 60
seconds, dangerous voltage levels may persist. Do not touch any power cable during
this time.
•
Do not ever open the converter. This is dangerous and invalidates the warranty.
The installation and cabling operations must be done when there is absolutely no voltage in
the entire electric cabinet. Make sure that the power switch on the converter is cut off from
the emergency circuit. The first time the cabinet is powered up, qualified technical personnel
must be present.