Siemens APOGEE P1 Communications Interface   

 

Point Database Cross Reference 

 

Point Number 

Subpoint Name 

Parameter 

CTRL ADDRESS 

Setup/Communications/Tec Option/Address 

2 ED_HVAC10  --- 

Freq Output 

Setup/Motor Control/Pattern Gen/Drive Frequency 

Freq Demand 

Setup/Seq & Ref/Reference/Speed Demand 

5 Speed 

Setup/Motor 

Control/Feedbacks/Speed Feedback 

6 Current 

Setup/Motor 

Control/Feedbacks/Motor Current 

7 Torque 

Setup/Motor 

Control/Feedbacks/Torque Feedback 

Power 

Setup/Motor Control/Motor Data/Power 

10 Drive 

KWH 

--- 

12 Runtime 

--- 

13 

DC Bus Volts 

Setup/Motor Control/Feedbacks/DC Link Volts 

14 Output 

Volts 

Setup/Motor 

Control/Feedbacks/Terminal Volts 

20 OVRD 

Time 

--- 

21 Direction 

Setup/Seq 

Ref/Reference/Reverse 

22 

Direction SP 

Setup/Inputs & Outputs/Dig In/Dig In 4/Invert 

23 

RUN 

Setup/Seq & Ref/Sequencing Logic/Running 

24 

RUN SP 

Setup/Seq & Ref/Sequencing Logic/Run Forward 

25 

Stop Mode 

Setup/Seq & Ref/Reference Stop/Run Stop Mode 

27 

Coast Stop 

Setup/Seq & Ref/Sequencing Logic/Not Coast Stop 

28 

Fast Stop 

Setup/Seq & Ref/Sequencing Logic/Not Fast Stop 

29 Day.Night 

Setup/Communications/Tec Option/Night 

30 

Curr Limit 

Setup/Motor Control/Current Limit/Current Limit 

31 

Accel Time 1 

Setup/Seq & Ref/Reference Ramp/Accel Time 

32 

Decel Time 1 

Setup/Seq & Ref/Reference Ramp/Decel Time 

33 

Stop Decel T 

Setup/Seq & Ref/Reference Stop/Stop Time 

34 

Fast Decel T 

Setup/Seq & Ref/Reference Stop/Fast Stop Time 

35 

Run Enable 

Setup/Seq & Ref/Sequencing Logic/Drive Enable 

37 

Reference SP 

Setup/Seq & Ref/Reference/Speed Setpoint 

40 

O/P Relay 1 

Setup/Inputs & Outputs/Dig Out/Dig Out 1/Value 

41 

O/P Relay 1 

Setup/Inputs & Outputs/Dig Out/Dig Out 2/Value 

42 

O/P Relay 3 

Setup/Inputs & Outputs/Dig Out/Dig Out 3/Value 

44 Flycatch 

EN 

Setup/Motor 

Control/Flycatching/Enable 

45 Flycatching 

Setup/Motor 

Control/Flycatching/Active 

50 

Analog 1 Out 

Setup/Inputs & Outputs/An Out/An Out 1/Value 

51 

Analog 2 Out 

Setup/Inputs & Outputs/An Out/An Out 2/Value 

52 

Analog 3 Out 

Setup/Inputs & Outputs/An Out/An Out 3/Value 

continued on next page…

Summary of Contents for Siemens APOGEE P1

Page 1: ...ltd Automation Group SSD Drives Europe cannot accept responsibility for damage injury or expenses resulting there from WARRANTY Parker Hannifin Ltd Automation Group SSD Drives Europe warrants the good...

Page 2: ...all performance endurance maintenance safety and warning requirements of the application are met The user must analyze all aspects of the application follow applicable industry standards and follow th...

Page 3: ...for your own information Unit used as a refer to Certification for the Inverter Component Relevant Apparatus Unit fitted Wall mounted Enclosure Application Area The equipment described is intended for...

Page 4: ...or the product s operation are correctly installed All control and signal terminals are SELV i e protected by double insulation Ensure all external wiring is rated for the highest system voltage Therm...

Page 5: ...0 2 User Connections to the Main Serial Port P1 3 DIL Switch SW1 Settings 3 Terminal Block TB1 Connections 4 Fitting and Connecting to the Technology Box 4 Wiring Diagrams 5 Initial Check for Connecti...

Page 6: ......

Page 7: ...ed twisted pair RS485 Configured using Function Block inputs Protocol tag access for defined P1 parameters Size Notation Part Numbers Size 1 HVAC10 drives use the 6053 APOG APOGEE Technology Box All S...

Page 8: ...drives by linking a Master PLC or APOGEE controller to one or more HVAC10 drives fitted with this module Plug this Communication Module on to the front of the HVAC10 drive by removing its terminal cov...

Page 9: ...th 4000ft 1200 metres Technology Box 6053 6055 Technology Box 1 2 3 4 5 6 TB1 Terminal Block 1 2 1 2 PLG1 BI SYNCH 1 Switch SW1 Figure 1 Option showing Terminal Block TB1 and DIL Switch SW1 DIL Switch...

Page 10: ...you must mount the Operator Station remotely using the Panel Mounting Kit with connecting lead 6052 The connecting lead enters the HVAC10 drive through the gland plate Remove the terminal cover and s...

Page 11: ...ON OFF 1 2 1 2 0V A B GND APOGEE Controller FL1 FL2 or FL3 connections Figure 3 2 Wire Wiring Diagram for the HVAC10 Size 2 3 Drive 0V DRIVE slave 1 2 3 4 5 6 B A 0V SCR B A 1 2 3 4 5 6 B A 0V SCR B A...

Page 12: ...C10 Size 2 3 6055 Technology Box The board does not have its own Health or Run LEDs The LEDs are either on the Operator Station or blank cover Module LED This indicates the set up state of the Technol...

Page 13: ...OT READY DISABLED Initialising FLASH IDLE No data is being received from Network Control Module LONG FLASH SOFT TIMEOUT Drive not addressed in the last 10 seconds ON OK Device has been addressed Note...

Page 14: ...rameter Select the node ADDRESS 0 to 31 Select the BAUD RATE default is 4800 Check the FAULT parameter for error messages and rectify if necessary When setting values for parameters from DSE Lite or o...

Page 15: ...fault external 5 MISSING no option fitted Also refer to Module LED page 6 VERSION Range 0x0000 to 0xFFFF The version of the Technology Option card If no option is fitted then the version is reset to z...

Page 16: ...Option Incorrect Technology Box Option fitted or selected Fit the correct Technology Box Option or select the matching value for the TYPE parameter in the TEC OPTION function block TYPE RS485 Set up...

Page 17: ...SP FWD 1 0 REV FWD 23 LDI RUN STOP 1 0 RUN STOP 24 LDO RUN SP STOP 1 0 RUN STOP 25 LAO Stop Mode 0 1 0 27 LDO Coast Stop FALSE 1 0 TRUE FALSE 28 LDO Fast Stop FALSE 1 0 TRUE FALSE 29 LDO Day Night DA...

Page 18: ...2 0 PCT 0 1 0 69 LAO Preset Spd 3 0 PCT 0 1 0 75 LDO Preset Sel MAIN 1 0 PRESET MAIN 77 LDI Purge NORMAL 1 0 PURGE NORMAL 79 LDI Tripped FALSE 1 0 TRUE FALSE 80 LDO Reset Fault OK 1 0 RESET OK 81 LAO...

Page 19: ...Reference Stop Run Stop Mode 27 Coast Stop Setup Seq Ref Sequencing Logic Not Coast Stop 28 Fast Stop Setup Seq Ref Sequencing Logic Not Fast Stop 29 Day Night Setup Communications Tec Option Night 3...

Page 20: ...reset Sel Setup Setpoint Funcs Preset Preset 1 Select Input 77 Purge Setup Misc Value Func Value Func 3 Input C 79 Tripped Setup Seq Ref Sequencing Logic Tripped 80 Reset Fault Setup Seq Ref Sequencin...

Reviews: