192-011006N8 PSD1 Installation Guide
192-011006N8 2019-07
09.10.19 09:27
65 (109)
100 µF per kW of the temporal medium value of the total power (transmi
power dissipation) in the axis system.
Example: PSD1-M_P020 (1175 µF) with one axis controller (440 µF)
Total power 15 kW, 100 µF/kW => 1500 µF required in the axis system.
Axis system: 1615 µF are sufficient.
Connection of a braking resistor on PSD1-M_P (mains module)
Minimum line cross section:
1.5 mm
2
Maximum line length:
2 m
Maximum intermediate circuit voltage: Depending on the
position of the
switches on the power module
(see
page 60)
Switch-on threshold:
Hysteresis:
5.12.8.1
Temperature switch mains module X40
Connector X40 Pin T1R, T2R
Temperature monitoring:
The temperature switch (normally closed contact) must be connected, unless an
error message will be issued.
Temperature switch/relay
No galvanic separation, the temperature sensor (normally closed contact) must
comply with the safe separation according to EN 60664.
If there is no temperature monitoring due to the connected braking resistor, the
T1R and T2R connections must be connected by a jumper.
Caution!
Without temperature monitoring, the braking resistor might be destroyed.
5.12.9.
X4: Inputs / Outputs of the mains module
Pin
Name
Function
1
24 VDC (output)
+24 VDC output (max. 340 mA)
2
GND24V
GND24V
3
24 VDC Dout (input)
24 VDC supply for outputs 0 ... 3
4
Nc
-
5
Input 0
Enable (High=Enable, Low=Disable)
6
Input 1
Quit (positive edge)
7
Input 2
Not defined
8
Input 3
Not defined
9
Output 0
Ready (High=ready , Low=not ready )
10
Output 1
Warning (High = no warning , low = warning)*
11
Output 2
Not defined
12
Output 3
Not defined
13
factory use
14
factory use
Axes must only be energized if A0 = ready = high!
* Warning
Capacity utilization of DC Bus = 90%
Temperature alarm: Rectifier 5 K to switch-off threshold