Parker Hannifin Corporation
– GS100 User Manual
26
8
Application Examples/How Do I…
Read/Write Sensor’s Message Rate
Example - Read Configuration Parameter, Message Rate
Identifier
D0
D1
D2
D3
D4
D5
D6
D7
18EFF980
0x81
2
0
FF
FF
FF
FF
FF
DA = 0x80 (Speed
Sensor)
SA = 0xF9
Command Type
Configuration
Parameter
Number
Read
Configuration
Reserved Bytes
Example - Response for Read Configuration Parameter, Message Rate
Identifier
D0
D1
D2
D3
D4
D5
D6
D7
18EF80F9
0x81
2
2
0x0A
0
00
00
00
DA = 0xF9
SA = 0x80 (Speed
Sensor)
Command
Type
Configuration
Parameter
Number
Response Data
D3(LSB),D4(MSB)
Unused Bytes
Example - Write configuration parameter, Message Rate
Identifier
D0
D1
D2
D3
D4
D5
D6
D7
18EFF980
0x81
2
1
0x0A
0
FF
FF
FF
DA = 0x80(Speed
Sensor)
SA = 0xF9
Command
Type
Configuration
Parameter
Number
Write
Operation
Data
D3(LSB),D4(MSB)
Reserved Bytes
•
For configuration parameter write operation, Speed Sensor will not send any acknowledgment or response.
Read/Write Example for Sensor’s Moving Average Filter Sample Size
Example - Read Configuration Parameter, Moving Average Filter Sample Size
Identifier
D0
D1
D2
D3
D4
D5
D6
D7
18EFF980
0x81
3
0
FF
FF
FF
FF
FF
DA = 0x80(Speed
Sensor)
SA = 0xF9
Command
Type
Configuration
Parameter
Number
Read
Configuration
Reserved Bytes
Example - Response for Read Configuration Parameter, Moving Average Filter Sample Size
Identifier
D0
D1
D2
D3
D4
D5
D6
D7
18EF80F9
0x81
0x03
0x0A
0x00
0x00
0x00
0x00
0x00
DA = 0xF9
SA = 0x80(Speed
Sensor)
Command
Type
Configuration
Parameter Number
Data
Unused Bytes
Example - Write Configuration Parameter, Moving Average Filter Sample Size
Identifier
D0
D1
D2
D3
D4
D5
D6
D7
18EFF980
0x81
3
1
0x0A
FF
FF
FF
FF
DA = 0x80(Speed
Sensor)
SA = 0xF9
Command
Type
Configuration
Parameter Number
Write
Operation
Data
Reserved Bytes