Chapter 2 – Installation
15
Step 2 – Conn24VDC Power
You must connect an ex24VDC power source to the Gem6K, as the next
drawing shows. Use the removable terminal connector that is supplied with the
drive.
With +24VDC applied, the drive’s internal control board will remain powered
when the primary AC power source is disconnected, and will maintain several
important functions, including communication diagnostics, position feedback, and
other logic functions.
DRIVE
POWER SUPPLY
VDC+
VDC–
+24V DC
24V RTN
RELAY COM
RELAY N.O.
Use twisted pair wiring
+24VDC Power Input
+24VDC Specifications:
Input voltage range:
19.2 – 28.8 VDC
Input current:
500 mA (maximum)
Functions available under +24VDC only:
position information (encoder or motor
position counters in drive)
communications
diagnostics
motor feedback
program execution not involving motion
(e.g., error programs, etc.)
Software status bit (see TASX command):
indicates “keep alive” is active: +24VDC
power only (AC power is disconnected)
CAUTION
Do not exceed 28.8VDC input voltage