6-10
Control Interfaces
6
6.5.7
Servo ON SERVO
The SERVO servo ON input signal is set to servo ON when the status is 1. In addition to this instruction, the
actual Servo ON/OFF status is affected by the setting of the SRV DS Servo ON disable switch on the front panel.
See the table below.
Servo ON/OFF
SERVO
SRV DS Servo ON
disable on the front panel
Actual servo status
Disabled
Status 0
Enabled
Disabled
Servo OFF
Status 1
Enabled
Servo ON
6.5.8
Current Limit Input
The current limit analog input signal gives a current limit from 0 to 100%, in proportion to a voltage input of 0 to
10V given by the external source. To enable this function, enable the
#206 Enabling current limit external
input
parameter. This parameter has been disabled by factory default setting.