background image

 

Parker Hannifin        

 

Filtration Group 
Racor Division  

 

DUAL FBO 

OPERATION AND MAINTENANCE INSTRUCTIONS 

SPARE PARTS 

 

DFBO-10-IN/DFBO-14-IN 

               

DFBO-14-MA 

 

 

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for DUAL FBO Series

Page 1: ...Parker Hannifin Filtration Group Racor Division DUAL FBO OPERATION AND MAINTENANCE INSTRUCTIONS SPARE PARTS DFBO 10 IN DFBO 14 IN DFBO 14 MA...

Page 2: ...NS 7 5 MAIN COMPONENTS 8 6 DESCRIPTION OF OPERATION 9 7 INSTALLING AND COMMISSIONING 10 7 1 Transporting and storing 10 7 2 Precautions 10 7 3 Installation drawings 11 8 USE OF SYSTEM 13 8 1 Precautio...

Page 3: ...e and safe use of the DFBO filter The manual provides instruction for operation and maintenance personnel Through correct use and maintenance the system can be kept in trouble free effective and econo...

Page 4: ...works When ordering spare parts or making arrangements for maintenance always quote the name of the device and its serial number as indicated on the type plate Any parts replaced for maintenance or pr...

Page 5: ...ction symbols are used in this manual PERSON SAFETY RISK Neglect of safety precaution may cause serious injury or death EQUIPMENT OR ENVIRONMENT RISK Incorrect use or maintenance of the device may cau...

Page 6: ...s use personal safety equipment required in the work or by law such as safety goggles earmuffs hard hat protective gloves safety boots and other necessary safety equipments Always have a first aid kit...

Page 7: ...ading Call for help Always aim to protect the environment Observe the local environment laws when disposing of filters hoses fuel oils or other waste material All detected leaks shall be remedied with...

Page 8: ...73309 031912 Parker Hannifin Racor Division 5 MAIN COMPONENTS 1 Filter housing 2 Filter bowl 3 Clamp 4 Filter element 5 Valve spool 6 Spool locator 7 Spool handle 8 Venting valve 9 Air exhaust port 1...

Page 9: ...ressure The valve directs the flow to one of the reservoirs according to the user set position First the oil is pushed from outside to in through a filter element which collect the dirt particles Afte...

Page 10: ...must be kept safe from mechanical effects hits excessive static loads and their transport must be performed without deforming or damaging the device packaging When transported the device packaging mus...

Page 11: ...Duplex Fuel Filter Separator 11 23 DUAL FBO 73309 031912 Operation and Maintenance Instructions Parker Hannifin Racor Division 7 3 Installation drawings 515 224 225 28 196 IN OUT 684 688 549...

Page 12: ...12 23 Duplex Fuel Filter Separator DUAL FBO Operation and Maintenance Instructions 73309 031912 Parker Hannifin Racor Division 100 138 205 1 6 5 441 7 175 68 1...

Page 13: ...not exceed specified pressure limits Check the differential pressure over the filter at regular intervals In normal operation one chamber is filtrating and the other chamber is on idle It is also pos...

Page 14: ...73309 031912 Parker Hannifin Racor Division 8 3 Changing the filtering idling chamber 1 Chamber B is filtrating according the text in front of the handle Pull the spool locator knob to release the sp...

Page 15: ...23 DUAL FBO 73309 031912 Operation and Maintenance Instructions Parker Hannifin Racor Division 2 After rotation 90 the spool may stop in the middle position Release the spool again by pulling the knob...

Page 16: ...ation and Maintenance Instructions 73309 031912 Parker Hannifin Racor Division 3 When the spool has been fully turned 180 make sure that the spool locator locks the valve spool Chamber A is filtrating...

Page 17: ...sion 8 4 Malfunctions Leaks Tighten joints at and around leaking point Replace the seals Make sure the system pressure is within specified limits Excessive pressure drop Make sure the filters have bee...

Page 18: ...er Never exceed any of the pressure values given by the manufacturer All parts replaced in conjunction with maintenance or repairs shall be original spare parts Remember the following notes and warnin...

Page 19: ...screws and turn the clamp 5 Take the filter bowl and the filter element of 6 Assemble the filter in reverse order Make sure that the filter element is right way round and the o ring seal is in its pl...

Page 20: ...hat no one may start the system during the service 1 Open the venting valves carefully to make sure that the system is pressureless 2 Filter can be drained from the bottom to minimize oil leakage from...

Page 21: ...Maintenance Instructions Parker Hannifin Racor Division 11 MANUFACTURER S CONTACT INFORMATION Parker Hannifin Filtration Group Racor Division Mail address 805 West Street Holly Springs MS 38635 United...