6.  Trouble Shooting 
Basis of troubleshooting is always a systematic 
approach.

  For suspect of a sluggish spool the valve may 

be flushed with clean pressure fluid.

7.  Accessories / Spare Parts
Accessories
The following accessories are available for the valve 
series DFplus pilot operated:
Bolt kit
D31FE 

ordering code BK385

D41FE 

ordering code BK320

D81/91FE 

ordering code BK360

D111FE 

ordering code BK386

Female connection
Code 0: 6+PE  ordering code 5004072
Code 5: 11-PE  ordering code 5004711
Code 7: 6-PE  ordering code 5004072

Spare Parts
Seal kit NBR
D31FE 

ordering code SK-D31FE

D41FE 

ordering code SK-D41FE

D81FE 

ordering code SK-D81FE

D91FE 

ordering code SK-D91FE

D111FE 

ordering code SK-D111FE

Hotline in Europe

Phone: 00800-2727-5374

Please direct technical product enquiries to:
Parker Hannifin 
Manufacturing Germany GmbH & Co. KG
Industrial Systems Division Europe
Gutenbergstr. 38
41564 Kaarst, Germany
Tel.: (+49) 181 99 44 43 0
E-mail: [email protected]

malfunction at hydraulic load runtime

- generally no function

- high frequent oscillation

- low frequent oscillation

- one way operation only

- speed variations at unchanging command

- different speeds depending on travel direction

- speed too low

- drifting without command

- poor dynamic
possible reasons for malfunction

corrective actions

X

hydraulic pump resp. motor defective

replace hydraulic pump resp. motor

X

X X X X X

X drive overloaded

reduce pressure resp. speed, increase valve size

X

X X X X X X X valve contaminated

clean pressure fluid, filter / flush valve

X

X

X hydraulic fluid too viscous / too cold

change fluid grade, provide operational temperature

X

X X

too low oil level within tank

refill pressure fluid

X X X

filter contaminated

replace filter

X

X

X X

supply voltage too low

keep supply voltage range

X

supply voltage carries too much ripple

reduce ripple

X

X

X

command signal too low

increase command signal

X

command signal carries too much ripple

reduce ripple

X

X

center position adjustment incorrect

check center position adjustment

X X

X

X X

contacts of central connector contaminated

clean contacts / replace plug

X

feed cable interrupted

fix feed cable

X X X X X

X X

wiring sequence incorrect

correct wiring sequence

X

X

feed cable without shielding

change cable grade

X

pilot pressure too low or failed

increase pilot pressure to min. 20 bar

X

X X

pilot pressure too low

increase pilot pressure to min. 20 bar

X pilot pressure too low

increase pilot pressure to min. 50 bar

  Troubleshooting in a hydraulic system requires 

detailed knowledge about function and con-
struction of the system. Therefore the work 
may exclusively be performed by qualified 
personnel.

Summary of Contents for D41FE

Page 1: ...e Operation Manual Series D 1FE Pilot Operated Design 30 Parker Hannifin Manufacturing Germany GmbH Co KG Industrial Systems Division Europe Gutenbergstr 38 41564 Kaarst Germany Tel 49 181 99 44 43 0...

Page 2: ...of the system and components and assuring that all performance endurance maintenance safety and warning requirements of the application are met The user must analyze all aspects of the application fol...

Page 3: ...g Name Plates 7 Work at the Valve 7 3 Important Details 7 Intended Usage 7 Common Instructions 7 Liability 7 Storage 7 4 Mounting Installation 8 Scope of Supply 8 Mounting 8 Operation Limits 8 Pressur...

Page 4: ...onic option NG06 pilot Proportional control High repeatability Pilot connections D 1 F C E Design series not required for ordering For details see Catalogue HY11 3500UK For details see Catalogue HY11...

Page 5: ...e valve The most important features are high dynamic actuator principle with special designed electronic driver closed loop controlled pilot valve and main spool Ensured fail safe behaviour constant c...

Page 6: ...tion class IP65 in accordance with EN 60529 with correctly mounted plug in connector Supply voltage ripple V 22 30 ripple 5 eff surge free Current consumption max A 3 5 Pre fusing A 4 0 A medium lag I...

Page 7: ...ded The manufacturer is not liable for warranty claims resulting from this Common Instructions We reserve the right for technical modifications of the described product Illustrations and drawings with...

Page 8: ...sscross with the following torque values D31FE 13 2 Nm D41FE 13 2 63 Nm D81 91FE 108 Nm D111FE 517 Nm Insufficient condition of the valve mounting surface migth create malfunction Incorrect mountingre...

Page 9: ...50 m For cable lengths 50 m consult Parker The connection cable is coupled to the female connector by solder joints Skinning lengths for the connecting cable The connection Code 5 requires a 11 PE fem...

Page 10: ...on observanceofthisinstruc tion may create irreparable damage of valve resp incorporated system parts The backshell nut of the cable gland has to be tighten with a suitable tool The target value for t...

Page 11: ...eries D 1FE Operation Manual 11 Parker Hannifin Corporation D_1FE 5715 688 UK CM 18 01 2019 Wiring Code 0 6 PE acc EN 175201 804 Code 5 11 PE acc EN 175201 804 Code 7 6 PE acc EN 175201 804 enable 1 D...

Page 12: ...e valve will reach its powerdownpositionspring actuatedindependently from the command signal value The enable function represents no safety ar rangementagainstunwantedvalveopera tion in terms of rules...

Page 13: ...nge filtration review valve flushing The overcurrent shutoff condition may be resetted by the actions below Code 0 Temporary disconnection of the supply voltage Code 5 Temporary disconnection of the e...

Page 14: ...ve parameter The chosen parameters may be optionally stored on the PC via the File menu with the menu item Save as data retrieving is always possible via the function Load file Extended functions The...

Page 15: ...pprox 0 5 Hz slowly green disable valve OK approx 1 Hz fast green valve error approx 10 Hz very fast green Closer information can be can be displayed via the ProPxD Parametrier software LED Error code...

Page 16: ...ustment of maximum signal span for negative output signal To match the command signal span to the valve operating range P7 MIN Adjustment of stroke step for valve side A at min operating threshold To...

Page 17: ...ault report about diagnosis 768 J8 Min supply voltage supervision Adjustment of the minimal supply voltage Below this supply voltage the valve switches off with an error message J9 Relay time out off...

Page 18: ...will be lost In principle parameters dedicated to a type which deviates from the connected valve may be edited However for data transmitting the correct valve has to be connected If parameters will b...

Page 19: ...pending on travel direction speed too low drifting without command poor dynamic possible reasons for malfunction corrective actions X hydraulic pump resp motor defective replace hydraulic pump resp mo...

Page 20: ......

Reviews: