3.5.6.
Mains connection Compax3H
Avoid permanent switching on and off so that the charging connection is not
overloaded.
Mains connection Compax3HxxxV4
Controller type
H050V4
H090V4
H125V4
H155V4
Supply voltage
Three phase 3*400VAC/480VAC
350-528VAC / 50-60Hz
Input current
54Aeff
93Aeff
118Aeff
140Aeff
60A 100A
125A
150A
Maximum fuse rating per
device(=short circuit
rating)
JDDZ class K5,
JDRX class H
JDDZ class H5,
JDRX class H
The terminal block of the drive can be found under the front cover. It is secured
with 2 screws at the bottom of the device. Remove the bottom cover in order to
access the conection clamps.
Make sure that all live parts are covered by the housing after installation.
Illustration of the connection clamps exemplarily for all sizes:
2
1
L1, L2, L3: 3 phase mains connection
M1, M2, M3: Motor connections
DC+, DC-: DC link voltage
(1) DBR+ und DBR-: Connection of external braking resistor
(2) AUX1, AUX2: only with C3H1xxV4 external supply (AC) for device ventilator L,
N
All
shields must be connected via a cable joint to the cable feedthrough plate.
Braking resistor and cable must be shielded if they are not installed in a control
cabinet.
The standard connection clamps of C3H090V4 and C3H1xxV4 are
not
suitable
for flat line bars.
Device protection