Parker EME
Mounting and dimensions
3.2
Mounting and dimensions
Ventilation:
During operation, the device radiates heat (heat dissipation). Please provide for
a sufficient mounting distance below and above the device in order to ensure
free circulation of the cooling air.
Please do also respect the recommended distances of other devices.
Make sure that the mounting plate is not exhibited to other temperature
influences than that of the devices mounted on this very plate.
The devices must be mounted vertically on a level surface. Make sure that all
devices are sufficiently fixed.
3.2.1.
Mounting and dimensions PSUP10/C3M050D6, C3M100D6,
C3M150D6
The devices are force-ventilated via a ventilator fan fixed to the lower part of the heat dissipator!
Mounting spacing: At the top and below: at least 100mm
Information on
PSUP10D6/C3M050D6, C3M100D6, C3M150D6
Mounting:
2 socket head screws M5
50mm
360mm
263mm
46mm
50,5mm
400mm
90°
Tolerances: DIN ISO 2768-f
192-
120148N13 2019-06
17