D-71
Programming
AC890PX AC Drive
LOCAL CONTROL
This block allows the available modes of Local and Remote operation to be customised. It also indicates the selected mode.
You can only switch between Local and Remote modes using the Keypad. Refer to Chapter 9: “The Keypad” - The L/R Key.
Parameter Descriptions
SEQ MODES
PREF: 94.01
Default: 0
Range: See below
Allows the source of sequencing commands to be selected. Local is the Keypad, Remote is an external signal. The modes
supported are:
Enumerated Value
:
Seq Mode
0 : LOCAL/REMOTE
1 : LOCAL ONLY
2 : REMOTE ONLY
REF MODES
PREF: 94.02
Default: 0
Range: See below
Allows the source of the reference signal to be selected. Local is the Keypad, Remote is an external signal. The modes
supported are:
Enumerated Value
:
Ref Mode
0 : LOCAL/REMOTE
1 : LOCAL ONLY
2 : REMOTE ONLY