Programming
D-42
AC890PX AC Drive
ENERGY METER
SETUP::MOTOR CONTROL::ENERGY METER
Designed for all Motor Control Modes.
This block measures the electrical energy used by the motor.
Parameter Descriptions
RESET
PREF: 113.01
Default: FALSE
Range: FALSE / TRUE
When RESET is set to TRUE, the ENERGY USED parameter is reset to zero automatically when the maximum value is reached.
When RESET is set to FALSE, the ENERGY USED parameter is held at the maximum value when the maximum value has been
reached
Changing this from FALSE to TRUE at anytime will cause the ENERGY USED parameter to be reset to zero.
POWER
PREF: 113.02
Default: 0.00 kW
Range: —.xx kW
This diagnostic shows the power being delivered to the load in kilowatts.
POWER
PREF: 113.03
Default: 0.00 hp
Range: —.xx hp
This diagnostic shows the power being delivered to the load in horsepower.
REACTIVE POWER
PREF: 113.04
Default: 0.00 kVAR
Range: —.xx kVAR
This diagnostic shows the reactive power being delivered to the load in kilo volt-amperes reactive.
ENERGY USED
PREF: 113.05
Default: 0.00 kW hr
Range: —.x kW hr
This diagnostic shows the total energy consumed by the load in kilowatt hours.
POWER FACTOR
PREF: 113.07
Default: 0.0
Range: —.x
This diagnostic shows the power factor estimate (between 0 and 1).
PF ANGLE
PREF: 113.08
Default: 0.00 deg
Range: —.xx deg
This diagnostic shows the power factor angle estimate.
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...