D-23
Programming
AC890PX AC Drive
DIGITAL INPUT
SETUP::INPUTS & OUTPUTS::DIGITAL INPUT
The digital input block converts the physical input voltage to TRUE or FALSE control signals.
Parameter Descriptions
VALUE
PREF: 8.02, 9.02, 10.02, 11.02,
12.02, 13.02, 14.02, 15.02,
16.02
Default: FALSE
Range: FALSE / TRUE
The TRUE or FALSE input.
Functional Description
There is a DIGITAL INPUT function block associated with each of the following terminals:
The Control Board has nine configurable digital inputs:
DIN1 is associated with terminal X15/01
DIN2 is associated with terminal X15/02
DIN3 is associated with terminal X15/03
DIN4 is associated with terminal X15/04
DIN5 is associated with terminal X15/05
DIN6 is associated with terminal X15/06
DIN7 is associated with terminal X15/07
DIN8 is associated with terminal X15/08
DIN9 is associated with terminal X15/09
Terminals X15/08 and X15/09 act as inputs by default. These terminals can also be set as outputs. Refer to DIGITAL
OUTPUT, page D-24.