Programming
D-8
AC890PX AC Drive
ANALOG INPUT
SETUP::INPUTS & OUTPUTS::ANALOG INPUT
The analog input block converts the input voltage or current into a value expressed as a percentage of a configurable range.
Parameter Descriptions
TYPE
PREF: 1.03, 2.03, 3.03, 4.03 Default: -10..+10V
Range: See below
The input range and type.
ANALOG INPUT 1 and ANALOG INPUT 2 are used for voltage measurement only.
ANALOG INPUT 3 and ANALOG INPUT 4 support all types.
ANALOG INPUT 5 is the differential of ANIN1 and ANIN2, see the Functional Description.
ANALOG INPUT 6 is -10.. +10 V. and its type is not user selectable.
Enumerated Value : Type
0 : -10..+10 V
1 : 0..+10 V
2 : 0..20 mA
3 : 4..20 mA
BREAK ENABLE
PREF: 3.04, 4.04
Default: FALSE
Range: FALSE / TRUE
Only available on ANIN3 and ANIN4. For input types that support sensor break detection (see Functional Description below),
this parameter may be used to disable sensor break detection. For input types that do not support break detection, this
parameter is FALSE.
BREAK VALUE
PREF: 3.05, 4.05
Default: -100.00 %
Range: -300.00 to 300.00 %
Only available on ANIN3 and ANIN4. The value that will appear as the VALUE output when BREAK is TRUE.