![Parker AC890PX Series Product Manual Download Page 236](http://html1.mh-extra.com/html/parker/ac890px-series/ac890px-series_product-manual_755704236.webp)
Certification
C-12
AC890PX AC Drive
EMC
Emissions Limits
Conducted
Frequency (MHz)
DB (
V)
Product Specific
Quasi Peak
Average
EN 61800-3
where I ≤100A
0.15 - 0.5
0.5 - 5.0
5.0 - 30.0
decreasing with log of frequency to:
100
86
90
70
90
76
80
60
Category C3
Table 17
where I ≥100A
0.15 - 0.5
0.5 - 5.0
5.0 - 30.0
130
125
115
120
115
105
Where these levels are too high and to ensure compatibility with other equipment, EMC filters are available from Parker
Hannifin Manufacturing.
Radiated
Frequency (MHz)
DB (
V)
Product Specific
Quasi Peak
EN 61800-3
30≤ f- ≤230
230≤ f- ≤1000
50
60
Category C3
(Table 18)
Measured at 10m
Where these levels are too high and to ensure compatibility with other equipment, Parker Hannifin Manufacturing can advise
on suitable counter-measures.