Trips & Fault Finding
9-19
AC890PX AC Drive
Fault Finding
Problem
Possible Cause
Remedy
Drive will not power-up
Fuse blown
Check supply details, replace with
correct fuse.
Faulty cabling
Check all connections are correct
and secure.
Check cable continuity
Drive fuse keeps blowing
Faulty cabling or connections
wrong
Check for problem and rectify before
replacing with correct fuse
Faulty drive
Contact Parker Hannifin
Manufacturing
Cannot obtain HEALTH state
Incorrect or no supply available
Check supply details
Motor will not run at switch-on
Motor jammed
Stop the drive and clear the jam
Motor runs and stops
Motor becomes jammed
Stop the drive and clear the jam
Motor won’t rotate or runs in reverse Encoder fault
Check encoder connections
Open circuit speed reference
potentiometer
Check terminal
Table 8-1 Fault Finding