6-15
Operating the Drive
AC890PX AC Drive
Starting Methods
The methods below can be used when the drive has the following default configurations from DSE 890 installed: Closed
Loop Vector, Sensorless Vector, Shaftless Printing, Shipping, Volts/Hertz.
IMPORTANT
DRIVE ENABLE must be True in all cases.
Single Wire Logic Starting
Use just DIGITAL INPUT 2 when the motor direction will always be the same. The motor will run while the RUN switch is
closed, and will stop when it is open.
Note that the SETUP::SEQ & REF::SEQUENCING LOGIC
::
NOT STOP parameter is active (FALSE - not wired to),
meaning that the drive will only run while the RUN parameter is held TRUE.
RUN
Digital Input 2
Sequencing Logic
JOG
NOT STOP
RUN FORWARD
CONTACTOR CLOSED
DRIVE ENABLE
NOT FAST STOP
NOT COAST STOP
TRUE
TRUE
TRUE
TRUE
24V
REMOTE REVERSE
REM TRIP RESET
TRIP RST BY RUN
TRUE
POWER UP START
FALSE
FALSE
FALSE
FALSE
FALSE
Figure 3.11
Wiring for Single Wire Starting (Default Configurations)