Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Page
D-151
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
SLIP COMP
SETUP::MOTOR CONTROL::SLIP COMP
Designed for VOLTS/Hz motor Control Mode.
The slip compensation function block allows the Drive to maintain motor speed in the presence of load disturbances.
Parameter Descriptions
ENABLE
PREF: 23.01
Default: FALSE
Range: FALSE / TRUE
For the slip compensation to be operational this must be TRUE.
MOTORING LIMIT
PREF: 23.02
Default: 150.0 rpm
Range: 0.0 to 600.0 rpm
The maximum trim that will be produced by the slip compensation block when the motor is driving the load (motoring).
REGEN LIMIT
PREF: 23.03
Default: 150.0 rpm
Range: 0.0 to 600.0 rpm
The maximum trim that will be produced by the slip compensation block when the motor is being driven by the load,
(regenerating).