PNO
Name
Path(s)
Type
Default
Range
Units
WQ
View
Notes MBus
0642
Comms Control Word.AUTO INITIALISE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
TECHNICIAN 2
01811
0643
Comms Control Word.EVENT TRIGGERED OP
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
TECHNICIAN 2
01813
0644
Control Word
Parameters::Motor Control::Sequencing
WORD
(bitfield)
0:SWITCH ON
1:ENABLE VOLTAGE
2:NOT QUICKSTOP
3:ENABLE OPERATION
7:RESET FAULT
10:USE COMMS CONTROL
11:USE COMMS REFERENCE
12:USE JOG REFERENCE
13:REVERSE DIRECTION
14:AUTO INITIALISE
15:EVENT TRIGGERED OP
NEVER
TECHNICIAN
01815
0645
Control Word.SWITCH ON
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01817
0646
Control Word.ENABLE VOLTAGE
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01819
0647
Control Word.NOT QUICKSTOP
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01821
0648
Control Word.ENABLE OPERATION
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01823
0652
Control Word.RESET FAULT
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01831
0655
Control Word.USE COMMS CONTROL
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01837
0656
Control Word.USE COMMS REFERENCE
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01839
0657
Control Word.USE JOG REFERENCE
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01841
0658
Control Word.REVERSE DIRECTION
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01843
0659
Control Word.AUTO INITIALISE
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01845
0660
Control Word.EVENT TRIGGERED OP
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01847
0661
Status Word
Parameters::Motor Control::Sequencing
WORD
(bitfield)
0:READY TO SWITCH ON
1:SWITCHED ON
2:OPERATION ENABLED
3:FAULTED
4:VOLTAGE ENABLED
5:QUICKSTOP INACTIVE
6:SWITCH ON DISABLED
9:CONTROL FROM COMMS
12:JOG OPERATION
13:REVERSE OPERATION
14:REFERENCE FROM
COMMS
15:STOPPING
NEVER
TECHNICIAN
01849
0662
Status Word.READY TO SWITCH ON
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01851
0663
Status Word.SWITCHED ON
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01853
0664
Status Word.OPERATION ENABLED
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01855
0665
Status Word.FAULTED
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01857
0666
Status Word.VOLTAGE ENABLED
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01859
0667
Status Word.QUICKSTOP INACTIVE
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01861
0668
Status Word.SWITCH ON DISABLED
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01863
0671
Status Word.CONTROL FROM COMMS
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01869
0674
Status Word.JOG OPERATION
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01875
0675
Status Word.REVERSE OPERATION
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01877
0676
Status Word.REFERENCE FROM COMMS
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01879
0677
Status Word.STOPPING
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01881
0678
Sequencing State
Parameters::Motor Control::Sequencing
USINT
(enum)
0:NOT READY TO SWITCH ON
1:SWITCH ON DISABLED
2:READY TO SWITCH ON
3:SWITCHED ON
4:OPERATION ENABLED
5:QUICKSTOP ACTIVE
6:FAULT REACTION ACTIVE
7:FAULTED
NEVER
TECHNICIAN
01883
Summary of Contents for AC30V Series
Page 34: ...Installation 4 16 AC30V series Variable Speed Drive Basic Speed Control Wiring...
Page 35: ...4 17 Installation AC30V series Variable Speed Drive APPLICATION 1 AUTO MANUAL CONTROL...
Page 36: ...Installation 4 18 AC30V series Variable Speed Drive Auto Manual Control Wiring...
Page 37: ...4 19 Installation AC30V series Variable Speed Drive APPLICATION 2 RAISE LOWER TRIM...
Page 38: ...Installation 4 20 AC30V series Variable Speed Drive Raise Lower Trim Wiring...
Page 39: ...4 21 Installation AC30V series Variable Speed Drive APPLICATION 3 PRESETS SPEEDS...
Page 40: ...Installation 4 22 AC30V series Variable Speed Drive Presets Speeds Wiring...
Page 41: ...4 23 Installation AC30V series Variable Speed Drive APPLICATION 4 PID CONTROL...
Page 42: ...Installation 4 24 AC30V series Variable Speed Drive PID Control Wiring...
Page 162: ...Sequencing Logic B 2 AC30V series Variable Speed Drive SEQUENCING DIAGRAM...
Page 325: ...E 2 E Plan Library AC30V series Variable Speed Drive Which then brings up the E Plan page...