Easy Start Guide

14. How to reset the Inverter to Factory Defaults

Page 14

This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright

The Inverter

Drive Supermarket and must not be reproduced or altered without prior written permission.

©

With the motor stopped, press the “M” key repeatedly until the
parameter list is shown.

14.1 Select parameter list.

The parameter list is prefixed with “F” as illustrated (left).

Press the “0” (stop) key to select the first (left) digit. This represents
the parameter group (F100, F200, F800 etc.)

Use the up and down keys to select parameter group F100.

14.2 Select parameter “group” 1.

Note: In parameter “group” mode, the “DGT” (digit) lamp is not
illuminated.

Use the up and down keys to select parameter F160. Press the “E”
key to edit the parameter value.

Note: In parameter mode, the “DGT” (digit) lamp is illuminated.

14.3 Select parameter F160.

Press the “0" (stop) key to select the last two (right) digits. This
represents the parameters within the group.

Press the “E” key to save the new value. The display will stop
flashing and may briefly go blank.

14.4 Set the value to 1 and save.

The initial value of 0 flashes. Use the up and down keys to change
this to 1.

Once the reset is complete the display will return to the parameter
list. The factory reset is complete.

Parker AC10 Series Inverter (to 22kW)

Summary of Contents for AC10 series

Page 1: ...a safety device All safety considerations including but not limited to Emergency Stop provision should be assessed separately and are outside the scope of this guide Parker AC10 Frequency Inverter to...

Page 2: ...nd configure a Potentiometer for remote speed control Contents Parameters Overview Parameters to set before use How to connect and configure a Run Stop switch with Forward Reverse selection Power and...

Page 3: ...tor phases determines the initial direction the motor turns Notes Important Use screened or armoured cable between the Inverter and Motor and ensure it is grounded as shown The supply must match the I...

Page 4: ...is not important They should be connected to the terminals marked L1 R L2 S and L3 T as shown In some cases these terminals may be marked L1 L2 and L3 only Notes The order of the three motor phases d...

Page 5: ...hanging from Delta to allow the motor to be changed back in future For safety purposes Star shown opposite is the default configuration for small motors usually to 3kW and is sometimes known as two at...

Page 6: ...power down 0 F228 Application Selection Defaults below are based on F228 0 Default is will suit most applications 5 different application Macros available 0 F801 Rated Motor Power kW Rated kW of the...

Page 7: ...roup mode the DGT digit lamp is not illuminated 6 2 Select the required parameter group Use the up and down keys to select parameter group F800 6 3 Select the required parameter Press the 0 stop key t...

Page 8: ...used to cycle through other values such as motor rpm current A and voltage U Parker AC10 Series Inverter to 22kW 7 1 Select the speed reference Press the M key repeatedly until the speed reference is...

Page 9: ...Motor Power kW Rated kW of the motor Set to match the motor nameplate eg 2 2kW 2200 F802 Rated Motor Voltage V Rated Voltage of the motor Set to match the motor nameplate eg V 230 F803 Rated Motor Cu...

Page 10: ...rated from 2kOhm to 5kOhm can be used eg 4 7kOhm The default output frequency at 0V is the minimum frequency of the Inverter To change this edit Parameter F112 The default output frequency at 10V is...

Page 11: ...on opposite When a connection is made between terminals 24V and DI3 the motor will run forward When terminals 24V and DI4 are connected the motor will run in reverse The selected direction of rotation...

Page 12: ...15 set to to select Run Fwd 15 F319 DI4 terminal function setting Default is 16 set to to select Run Rev 16 11 1 Parameters to change for remote Run Stop Two suitable 2 position NO Normally Open swit...

Page 13: ...rse Select Open Forward Closed Reverse 16 12 1 Parameters to change for remote 3 wire control Note that the Forward Reverse switch can be used to set the direction when the motor is stopped or running...

Page 14: ...or manual issued by the manufacturer for details 13 2 Connecting the Resistor The braking resistor may get hot during operation Ensure that it is suitably mounted so any heat generated will not affec...

Page 15: ...0 F800 etc Use the up and down keys to select parameter group F100 14 2 Select parameter group 1 Note In parameter group mode the DGT digit lamp is not illuminated Use the up and down keys to select p...

Reviews: