023-064X Technical Manual
10
6
MT Alliance installation
Log into MT Alliance. You must have
technician refrigeration configuration
permissions.
Enter configuration Mode.
Select and zoom in the view where the sensor is located.
From the
Components box
Pick and drop a Sensor
Then select
Absolute Gas Concentration Type
,
Local Source
,
Micro Thermo
Manufacturer and the
Sensor Model
and gas type you are going to monitor (pre-defined sensor model will be available in
version MTA 8.5. For previous version create a user defined model at the next section or use the 023-
034X series)
Click OK then click on the new button.
Select the
Detail
tab and enter a sensor name in the
Identification
field and put
“Normal reading is
less than 10 ppm when no gas is present” in the
Notes
field (put 2 ppm more than 1% of full range)