LT8540
P10 INSTALLATION INSTRUCTIONS
Spillage Test Procedure.
Light the appliance on maximum setting.
Close all the doors and windows.
After five minutes fit the smoke match within match holder and position as illustrated in Figure 13
with the head of the match just inside the inlet air channel.
Run the match along the edge of the inlet air channel. All smoke must be drawn into the inlet
channel if the spillage test is satisfactory.
If spillage occurs wait a further five minutes and repeat the test.
Repeat the test with doors open and with any extractor fans in other rooms in operation.
If spillage is detected the cause must be discovered and the fault corrected. If the fault cannot
be corrected, disconnect the fire from the gas supply and seek expert advice. Spillage can be
caused by a restriction in the flue system, down draught or insufficient ventilation into the room
where the fire is installed.
Summary of Contents for P10
Page 9: ...P a g e 8 LT8540 P10 USERS INSTRUCTIONS RH Inlet Cover ...
Page 11: ...P a g e 10 LT8540 P10 USERS INSTRUCTIONS No 3 Shape ...
Page 12: ...P a g e 11 LT8540 P10 USERS INSTRUCTIONS No 4 Shape No 5 Shape No 6 Shape ...
Page 13: ...P a g e 12 LT8540 P10 USERS INSTRUCTIONS No 7 Shape No 8 Shape No 9 Shape ...
Page 14: ...P a g e 13 LT8540 P10 USERS INSTRUCTIONS No 10 Shape No 11 Shape No 12 Shape ...
Page 15: ...P a g e 14 LT8540 P10 USERS INSTRUCTIONS No 13 Shape No 14 Shape No 15 Shape ...
Page 34: ...P a g e 33 LT8540 P10 SERVICE FAULT FINDING INSTRUCTIONS Fault Finding Charts ...
Page 35: ...P a g e 34 LT8540 P10 SERVICE FAULT FINDING INSTRUCTIONS ...
Page 36: ...P a g e 35 LT8540 P10 SERVICE FAULT FINDING INSTRUCTIONS ...
Page 37: ...P a g e 36 LT8540 P10 SERVICE FAULT FINDING INSTRUCTIONS Wiring Diagram ...
Page 46: ...P a g e 45 LT8540 ...
Page 47: ...P a g e 46 LT8540 ...