Esprit 728 Ultra & 738 Ultra
3
Figure 3: Connecting the Backup Battery
2.3.3
Auxiliary Power Terminals
The
AUX
+ and
AUX
- terminals on the control panel can provide a maximum of 450mA (728 Ultra) or 500mA (738 Ultra)
12Vdc (200mA 12Vdc for 24Hr stand-by on UL/cUL installations). You can use the auxiliary power supply to power the
motion detectors, keypads and other accessories in your security system. Their combined current consumption should
not exceed 650mA (728 Ultra) or 700mA (738 Ultra). See Table 1 for current consumption levels. The auxiliary supply
is microprocessor-protected against current overload and automatically shuts down if the current exceeds 650mA (728
Ultra) or 700mA (738 Ultra). Auxiliary power will resume once the overload condition is restored and within 1 to 60
seconds of performing the dynamic battery test.
* Do not use the 646 LED and 642 LCD keypads for UL installations. Both the 646 LED keypad and the 642
LCD keypad are not UL listed.
2.3.4
Battery Test
The control panel conducts a dynamic battery test under load every 60 seconds. If the battery is disconnected, or its
capacity is too low, the
[1]
key in the trouble display mode will illuminate. Key
[1]
will also illuminate if the battery
voltage drops to 10.5 volts or less when the control panel is running on the back-up battery (no AC). At 8.5 volts, the
panel shuts down and all outputs close.
2.3.5
Keypad Function Test
We recommend conducting a power-up test on keypads installed far from the control panel. To do so, temporarily
connect the keypads near the control panel and connect the transformer. After 10 seconds, begin entering random
commands on the keypad and verify that the keypad beeps in response to these commands. Then open a zone to
ensure that the keypad and the control panel are responding to these signals. If the keypad does not respond and
indicator lights do not illuminate, verify that approximately 16Vac is present at the AC terminals. If AC is present, check
the keypad wiring and verify that there isn't a short between the black and red keypad wires. If the keypad does not
respond, please contact your local Paradox Distributor.
2.4
Telephone Line Connection
Connect the incoming telephone company wires into the
TIP
and
RING
connections of the control panel. Then run the wires from
T
-
1
and
R
-
1
to the telephone system as shown in Figure 4.
If the
STATUS
LED is always ON, the panel is using the phone line.
Figure 4: Telephone Line Connection
Table 1: Current Consumption Table
Modules
Current Consumption
Typical
Maximum
Motion Detectors (see detector instructions for details)
10 to 50mA
636/646* LED Keypads
15mA
30mA
642* LCD Keypads
40mA
55mA
708 Ultra Stand-Alone Digital Dialer
50mA
50mA
MG-RCV3 Wireless Expansion Module
50mA
50mA
Backup battery
12Vdc 4Ah / 7Ah
UL / cUL
12Vdc 7Ah only