Panduit UTFMRDU User Manual And Installation Manual Download Page 1

 

 

 

 

Panduit 5 kVA 208 to 120 VAC Step-Down 

Transformer

 

User’s Guide and Installation Manual V2.0

 

Model(s): UTFMRDU

 

 

 

 

Summary of Contents for UTFMRDU

Page 1: ...Panduit 5 kVA 208 to 120 VAC Step Down Transformer User s Guide and Installation Manual V2 0 Model s UTFMRDU...

Page 2: ...unting and Installation Instructions 4 Rack Mounting 4 Four Post Rack Mounting 5 Tower Mounting 8 Section 3 Transformer Overview and Features 9 Key Features 9 Step Down Transformer Physical Features a...

Page 3: ...heavy Use caution during installation Before moving the Step Down Transformer be sure to use the original packaging materials to prevent or reduce the possibility of personal injury or damage to the p...

Page 4: ...nstallation The transformer may be installed and operated by a trained qualified layman Only use the input cable supplied with the transformer Input power is restricted to 208 VAC WARNING Do not use 2...

Page 5: ...ack mounting If the included hardware is not suitable for your rack contact the rack manufacturer to obtain proper mounting accessories It is recommended to mount the transformer near the bottom of th...

Page 6: ...front to rear distance of 460 1000 mm 18 to 39 inches 1 Install the URMKIT2 rail kit a Install the front side of the rail kit with 3x Phillips Pan Head M5 screws see figure below on each rail Do not...

Page 7: ...f the first locations above the top rail kit screw see figure below 2 Install the mounting brackets included a Remove the 2x Phillips Flat Head M4x8 screws from the front of each side of the transform...

Page 8: ...transformer slide the transformer into the rack on the rail kit see figure below b Align the mounting brackets with the screw holes on the rack and secure the UPS with the supplied 4x Phillips Hex He...

Page 9: ...the stabilizing tower mounting feet Only the stabilizing tower mounting feet containing foam pads included in the kit are to be used Do not mount the transformer in a tower configuration if the unit i...

Page 10: ...AC Output voltage Operable at 60 Hz and 50 Hz One NEMA L6 30P input plug One manually resettable 25A input breaker Twelve NEMA 5 20R outlets Four manually resettable 20 A breakers for the 5 20R outlet...

Page 11: ...er the Transformer unit with 240 VAC Input Breaker The Step Down transformer input cord is equipped with an input breaker rated at 25A The input breaker has a manual reset switch Outlet groups will be...

Page 12: ...000 VA load 1500 VA each The Step Down Transformer also contains a pass through 208 V NEMA L6 30R outlet group labeled GROUP 5 Total rated capacity of the Transformer is 5000 VA distributed between th...

Page 13: ...nput Cord 2 Input Breaker 3 L6 30R Output Group 5 4 NEMA 5 20R Group 1 Output 120 VAC 5 NEMA 5 20R Group 2 Output 120 VAC 6 NEMA 5 20R Group 3 Output 120 VAC 7 NEMA 5 20R Group 4 Output 120 VAC 8 Outp...

Page 14: ...ltage Group 5 208 VAC L1 L2 PE Groups 1 4 120 VAC L N PE Output Frequency 50 60 Hz Maximum Output Power Total distributed 5000VA 5000W Maximum Output Power per Outlet Group Group1 1500VA 1500W Group2...

Page 15: ...ating elevation 0 1000 meters 1000 meters requires derating Noise level 45dB CONFORMANCE Safety cUL UL 1778 5th Edition CSA C22 2 NO 107 3 14 FCC FCC Part 15 Subpart B Class A ANSI C63 4 2014 Transpor...

Page 16: ...ected and powered but the fan is not functional Input voltage is insufficient The fan may have jammed or malfunctioned Verify input voltage is within nominal range Power off unit and clear obstruction...

Page 17: ...ANUAL 16 If the troubleshooting procedures do not solve the problem contact Panduit Customer Support at cs panduit com or 1 800 777 3300 with the following information Product SKU and serial number De...

Page 18: ...t 4 pieces Rack Mounting Brackets 2 pieces Safety Warning Sheet 1 sheet Rack Rail Mounting Kit URMKIT2 1 kit o Left Slide Rail 1 rail mechanism o Right Slide Rail 1 rail mechanism o Phillips Pan Head...