SMARTZONE UPS INSTALLATION MANUAL
4
Section 1
– Overview
This Manual provides the instructions for installing the Uninterruptable Power Supply
Units, the External Battery Pack Units, the Maintenance Bypass Switch Unit, and the
UPS/EBP Battery Cartridges. Refer to the table below for all SKUs included in this
Installation Manual.
All units should be installed in an environment that is within the operating parameters of
the units.
•
Operating Temperature:
0-40
°
C (no derating)
•
Operating Humidity:
0-95% (non-condensing)
•
Max. Operating Elevation: 3000 m (10% derating); 1000 m (no derating)
•
Protection Class:
IP20
All units require mounting support when mounted in a rack. A rail mounting kit and a
tower mounting kit are provided with most units. The rail mounting kit is used for the
preferred mounting, in a four-post rack. The tower mounting kit is used for mounting on
the floor or desk in a vertical orientation.
Refer to the appropriate Appendix in this manual for a detailed list of the components
included with the product.
The following three sections provide the information on handling, installing, and wiring
the SKUs in this manual. There are many common installation steps between the
various unit models. Subsections are provided for unique installation steps that must be
completed on specific models.