Panduit DPOE24S1XY User Manual Download Page 1

 
 

DPoE

™ 

Power Patch Panel 

User Manual 

For Parts DPOE24U1XY, DPOE24S1XY, DPOE12U1XY 

 

 

 

 

 

 

 

 
Copyright © 2008 PANDUIT Corp. All rights reserved. No part of this book shall be reproduced, stored in a retrieval 
system, or transmitted by any means, electronic, mechanical, photocopying, recording or otherwise, without written 
permission from 

PANDUIT

. No patent liability is assumed with respect to the use of the information contained herein. 

 
Although every precaution has been taken in the preparation of this book, 

PANDUIT

 assumes no responsibility for 

errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained 
herein. 

 

 
 
 

Part # PN378E 

Published October 2008 

Summary of Contents for DPOE24S1XY

Page 1: ...ical photocopying recording or otherwise without written permission from PANDUIT No patent liability is assumed with respect to the use of the information contained herein Although every precaution ha...

Page 2: ...rom another country The products presented in this user s guide are not designed intended authorized or warranted to be suitable for use as components in systems used in any life support or critical a...

Page 3: ...Requirements 19 Installing the DPoE Element Manager Software 20 Connecting the DPoE Element Manager Host Computer to the DPoE Power Patch Panel 21 DPoE Element Manager Operation 21 Graphical User Int...

Page 4: ...gures Figure 1 DPoE Power Patch Panel Front View 6 Figure 2 DPoE Power Patch Panel Rear View 7 Figure 3 System Level Opening Screen 22 Figure 4 View Panel Screen 31 Figure 5 View Device Screen SNMP Se...

Page 5: ...DPoE Element Manager Log Messages 49 Table 13 DPoE Power Patch Panel Firmware Update LED Status 52 Table 14 Power Supplies Available from PANDUIT 53 Table 15 Package Contents 53 Table 16 PANDUIT Corp...

Page 6: ...out the need for separate passive patch panels NOTE DPoE Power Patch Panels cannot be used for analog or non Ethernet devices While the DPoE Power Patch Panel may be used as a standalone device it can...

Page 7: ...devices and allows centralized power management by the network operator Combining PoE Power with patch panel functionality for Ethernet Connections Other vendors use a separate Power Hub architecture...

Page 8: ...e event of low power conditions a NMS working in conjunction with the DPoE Power Patch Panels can use the pre established port priorities to ensure mission critical ports on the network of panels cont...

Page 9: ...0 watt rectifier for use in the DPOEPWRCU chassis CORD A Power cord for Australia CORD E Power cord for Europe CORD S15 Power cord for North America CORD J15 Power cord for Japan CORD U Power cord for...

Page 10: ...Do not exceed a total length of 35 feet Verify the above contents arrived in good condition If not contact PANDUIT Technical Support Table 3 PANDUIT Corporation Contact Information PANDUIT Technical S...

Page 11: ...green and yellow striped grounding strap to the panel via the unthreaded hole nearest the power connector Next install the panel into a grounded rack using the appropriate screw set provided to ensure...

Page 12: ...chain fashion as shown Once all of the connections are made the DPoE Element Manager or another Network Manager will be able to communicate with all the panels over this daisy chain of connections Se...

Page 13: ...NICATION LINE HAS BEEN DISCONNECTED AT THE NETWORK INTERFACE NOTE Never install wiring in a slot previously used for a larger gauge wire 10 Using the recommended punchdown tool PANDUIT part number PDT...

Page 14: ...e power harness wires to the supply wires A crimping tool such as the PANDUIT part number CT 100 may be used The provided butt splices PANDUIT part number BSV14X support 14 16 AWG solid or stranded wi...

Page 15: ...tatus LED above the IN management port will stay amber and the network status LED above the OUT management port will turn off This indicates that the panel is actively requesting address information f...

Page 16: ...andards Also try to connect the device to another port to see if it powers on 4 The port Administration Control setting is set to OFF in the DPoE Element Manager The DPoE Element Manager must be used...

Page 17: ...ption Status of Power Ports Off Off No Power is being supplied to the panel Power is NOT being delivered to the ports on the panel Green Flashing System operating normally Power may be delivered down...

Page 18: ...hould be checked to ensure proper wiring has been followed Power is NOT being delivered down this port on the panel Table 9 Network Status LED Indications LED Color Network LED Status Description Note...

Page 19: ...ssor or equivalent RAM 128 MB of RAM 256 MB recommended Hard Disk Space 45 MB of available hard disk space Network Access 10 100 Ethernet card CD ROM Drive Software Operating System Any Windows Vista...

Page 20: ...le Launch exe Once all required support software is installed the installation screen will be displayed For security purposes the network operator will then be given the opportunity to restrict the DP...

Page 21: ...to anything IMPORTANT Directly connecting a PC to the panel will either require the PC to be setup as a DHCP Server or require the DPoE Power Patch Panel to be setup for static IP addressing The pane...

Page 22: ...els Likewise configuration changes can be made at the network panel or port level The Tree View of the Network area provides a hierarchical display of each patch panel within the network using the con...

Page 23: ...l time display indicates the communication status between the DPoE Element Manager and the DPoE Power Patch Panels By adding additional UserNames to the DPoE Element Manager the network operator can a...

Page 24: ...an be used to collect this information during installation When installing multiple DPoE devices simultaneously it is very important to record the MAC address for each panel Since multiple panels will...

Page 25: ...er and the DPoE Power Patch Panels For security reasons these fields should be changed from their defaults Care should be taken however as the SNMP Community fields are case sensitive and will read in...

Page 26: ...Power Patch Panel information will be populated in the DPoE Element Manager the Start button will initiate the Discover capability TIP In addition to the Discover capability the DPoE Element Manager...

Page 27: ...ring its specific attributes into the DPoE Element Manager is an integral part of the provisioning activity Loading this information into the DPoE Element Manager enables it as well as Network Managem...

Page 28: ...ay be a problem with the network connection itself The DPoE Element Manager reflects physical location information and power status based on the last time this information was refreshed In order to wo...

Page 29: ...used to associate the discovered device with the information contained on the installation worksheet and the Panel Attributes can now be entered 6 Double click on the row in the table containing the...

Page 30: ...oE Power Patch Panel Fill out per the example shown on right Click the OK button and the Device Physical Location information will be added to the device attributes field 8 Once all of the desired inf...

Page 31: ...intuitive physical location information that is stored in each panel The DPoE Element Manager makes it easy to administer the deployed network of DPoE Power Patch Panels When a specific panel is sele...

Page 32: ...set for this device This screen cannot be used to modify the configuration SNMP information The SNMP configuration can be edited selecting the Edit Panel Info button on the right side tool bar Edit Pa...

Page 33: ...ple port 5 and the selected port will highlight with a flashing yellow indicator You will receive a dialog box on screen stating that the EMS is obtaining the latest information for the selected port...

Page 34: ...e Rack Space Position field refer to Provisioning the Panel for more information Once these values are set in the DPoE Element Manager this information will be transmitted and stored in the DPoE Power...

Page 35: ...ct the number of times a SNMP message retry occurs prior to receiving this Timeout error message The SNMP Retry function enables a choice of the amount of times the SNMP message is retried Once a devi...

Page 36: ...one panel to another The Copy Panel and Paste Panel options under the Tools pull down menu provide an easy mechanism to perform this task Once a panel is highlighted in the Tree View of the Network a...

Page 37: ...nto new units prior to configuration A dialog box will appear allowing device information to be exported for All Devices Devices that are in the Selected Rack Room or for the Selected Device The Refre...

Page 38: ...atabase in memory is erased Restoring Device and Port Information The Import function allows retrieval of saved device and port data that has been previously extracted and saved to a file using the Ex...

Page 39: ...device If a device is selected incorrectly it is possible to overwrite a 24 port configuration information into an 8 port device only the data representing the first 8 ports will be used Conversely a...

Page 40: ...will bring up the configuration information for that individual port This is the same screen that will appear by double clicking an individual port on the Visual Display of the Front Panel portion on...

Page 41: ...ort Screen Clicking on the Edit button will bring up a screen to edit individual ports on a DPoE Power Patch Panel If the network operator were simultaneously configuring multiple ports the Multiple P...

Page 42: ...r a closed circuit condition and will not apply power until a load is detected across the circuit In Forced mode the device port will deliver power without performing a detection classification If not...

Page 43: ...tial listing of all messages received by the DPoE Element Manager displaying them in a first in first out manner That is the most recently received messages are listed at the top of the window and the...

Page 44: ...C addresses Panel name or range of panel names Port number or range of port numbers Specific message types Export Log By clicking on the Export Log button the operator is given the option of exporting...

Page 45: ...the racks in a panel or a single panel within a rack By using the E mail mechanism the network operator can assign specific e mail addresses to be notified of network events For example the DPoE Elem...

Page 46: ...anel of the E mail Settings the right panel is used to select which message categories will be sent to that e mail address refer to DPoE Element Manager Log Messages for more information on each of th...

Page 47: ...User Manual Part Number PN378E 47 Panel level searches can be conducted by any combination of MAC address Panel Name Rack Name Rack Space Location Hardware Version IP Address Physical Location Power S...

Page 48: ...378E 48 Port level searches can be conducted by any combination of Port Number PD Type Work Area Location Administration Control Detection Status Power Priority Power Classification Legacy Control NOT...

Page 49: ...Device Power Above Threshold Major The power consumption at the device has risen above the Power Warning Threshold Device Power Below Threshold Major The power consumption at the device has fallen be...

Page 50: ...panels in the racks in the same fashion as they are wired in the network racks Either the rack slots are numbered from with the highest rack positions at the top Descending or the highest rack positio...

Page 51: ...st point to the directory where the new DPoE product file is stored 3 The Update Firmware under the option Tools pull down menu opens a window that identifies the IP address device type and device nam...

Page 52: ...Ethernet Switch Initialization 00 01 seconds Amber Solid DHCP Initialization 01 100 seconds Green Blink DHCP complete Red rapid Blink Green Blink Image transfer and update in progress 5 7 minutes Red...

Page 53: ...PWRR1250 1250 watt rectifier for use in the DPOEPWRCU chassis CORD A Power cord for Australia CORD E Power cord for Europe CORD S15 Power cord for North America CORD J15 Power cord for Japan CORD UPWR...

Page 54: ...S 30 The PAN TY S are used to secure the shielded cable to the rear shield and secure the shield Verify the above contents arrived in good condition If not contact PANDUIT Technical Support Table 15 P...

Page 55: ...at the planned rack position 4 Record the rack space position on the Installation Worksheet 5 Prepare the shielded cables for termination using the figures appropriate for the type of cable used Cauti...

Page 56: ...sponding to a EIA TIA 568A or EIA TIA 568B configured data pairs wiring sequence must be used Table 16 Color Coded Wire Positions for 802 3af 2003 Compliant Devices Pin Outs EIA TIA 568A Pin Outs EIA...

Page 57: ...TE GREEN 1 WHITE ORANGE 2 GREEN 2 ORANGE 3 WHITE ORANGE 3 WHITE GREEN 6 ORANGE 6 GREEN 7 WHITE BLUE 7 WHITE BLUE 8 BLUE 8 BLUE 7 For best performance the cable pair twists should be maintained as clos...

Page 58: ...be able to communicate with all the panels over this daisy chain of connections See Panel Provisioning the for more information Power Requirements 10 If the panel is being powered by an individual pow...

Page 59: ...cal Support for more information about connecting the redundant B Feed Power 13 Lightly tug on the butt spliced connections to verify that the butt splices are secure 14 Plug the connector into the ba...

Page 60: ...s configured for Dynamic Host Control Protocol DHCP address assignment and a cable is NOT connected to the IN management port on the rear of the panel the panel status LED will blink green If the DPoE...

Page 61: ...om the front of the unit If the panel were set to static IP addressing rather than DHCP the network status LED above the IN management port will immediately turn green If the panel were set to static...

Page 62: ...et IEEE 802af specifications Typical per port power output IEEE 802 3af 2003 compliant power 15 4 watts port 46VOUTDC 350mA Maximum overall power consumption 490 Watts 57VINDC 8 6 A Mounting Option Mo...

Page 63: ...cal and Electronic Engineers IP Internet Protocol LED Light Emitting Diode MAC Media Access Control MHz Megahertz NMS Network Management System o d Outside Diameter PC Personal Computer PD Powered Dev...

Page 64: ...roducts freetools index aspx TFTPServer 3Com Freeware ftp ftp 3com com pub utilbin win32 3cs117 zip Weird Solutions Shareware http www weirdsolutions com weirdSolutions files products desktopSoftware...

Page 65: ...PANDUIT DPoE Power Patch Panel User Manual Part Number PN378E 65 Click Yes Click Next...

Page 66: ...Patch Panel User Manual Part Number PN378E 66 Click Finish Now run the program Move your mouse to the Start Menu lower left corner Start Menu All Programs Solar Winds Free Tools TFTP Server Go to the...

Page 67: ...configured correctly After the download works you will see something like this on the screen that shows the file transfer Note If you are using a TFTP server from another vendor they may have some us...

Reviews: