background image

 

VeriSafe AVT 

 

B21075 

Rev: 00  04-2018 

Absence of Voltage Tester 

Instruction Manual 

Models: VS-AVT2-C02L03, VS-AVT2-C08L10 

For use in Hazardous Locations Class I, Division 2 or equivalent Class I, Zone 2 

© Panduit Corp. 2018 

 

Original Instructions 

 

 

 

 

 

TO REDUCE THE RISK OF INJURY, USER 
MUST READ INSTRUCTION MANUAL 

 

 

 

NOTE: In the interest of higher quality and value, Panduit products are 
continually being improved and updated. Consequently, pictures may vary from 
the enclosed product.  

 

NOTE: Updates to this Instruction Manual may be available. Check 
www.panduit.com for the latest version of this manual. 
 

Email: 

[email protected] 

 

EU Website: 

www.panduit.com/emea 

 

EU Email:  

emeatoolservicecenter 

@panduit.com

 

 

www.panduit.com 

Technical Support: 

Tel:  1-866-405-6654 

 
 

Panduit Europe •  EMEA Service Center 

Almelo, Netherlands 

Tel: +31-546-580-452  •  Fax: +31-546-580-441 

The VeriSafe Absence of Voltage Tester is a permanently-mounted tester that is used to verify a circuit is de-
energized prior to opening an electrical enclosure. Once installed, a push of a button enables qualified electrical 
workers to verify the absence of voltage and see an active indication when the absence of voltage is confirmed. 
The Indicator Module is designed for a 30-mm notched panel knockout and the Isolation Module can be mounted 
to DIN rail or surface mounted using screws. 

Summary of Contents for 1311914

Page 1: ... version of this manual Email techsupport panduit com EU Website www panduit com emea EU Email emeatoolservicecenter panduit com www panduit com Technical Support Tel 1 866 405 6654 Panduit Europe EMEA Service Center Almelo Netherlands Tel 31 546 580 452 Fax 31 546 580 441 The VeriSafe Absence of Voltage Tester is a permanently mounted tester that is used to verify a circuit is de energized prior ...

Page 2: ...ents 4 Output Contacts 4 Technical Specifications 5 Dimensions 7 Schematics 8 Installation Considerations 11 Installation Instructions 13 Commissioning Checklist 15 Operating Instructions 16 Troubleshooting 17 Maintenance 18 Battery Replacement 18 AVT System Cable Removal 19 O ring Replacement 19 Cleaning Instructions 19 Visual Inspection 19 Warranty 20 ...

Page 3: ...emble or heat above 85 C incinerate or expose contents to water Use only the included AVT System Cable or approved replacement cables to connect the Isolation Module and Indicator Module Do not use a standard Ethernet cable Battery AVT System Cable and O rings can be replaced No other part of the product is serviceable Do not attempt to open the Indicator Module or Isolation Module for repair or m...

Page 4: ...charger démonter ou chauffer au dessus de 85 C incinérer ou exposer le contenu à l eau Utilisez uniquement le câble système AVT inclus ou les câbles de remplacement approuvés pour connecter le module d isolement et le module indicateur N utilisez pas de câble Ethernet standard La batterie le câble du système AVT et les joints toriques O rings peuvent être remplacés Aucune autre partie du produit n...

Page 5: ...solation Module The outputs are normally open and close only when the green Absence of Voltage Indicator is illuminated By wiring to these contacts the AVT can be used as an input to a control system as well as log when the absence of voltage was verified Recommended Wiring For redundant monitoring of output state Output Contact Specifications Two channel single pole normally open Relay closure up...

Page 6: ...rements for safety related systems and for equipment intended to perform safety related functions functional safety General industrial applications including corrigendum 1 EN 55011 CISPR 11 Industrial scientific and medical equipment Radio frequency disturbance characteristics Limits and methods of measurement IEC EN61000 3 2 IEC EN61000 3 3 Electromagnetic compatibility EMC Part 3 2 Limits Limits...

Page 7: ...ection specified is related to the Indicator Module only To meet the TYPE UL NEMA and CSA 1 12 4 4X 13 IP66 or IP67 requirements mount on a flat surface of an enclosure meeting the appropriate UL TYPE or NEMA rating Verify that the seal and o rings are clean to ensure proper sealing Environment Operating Temperature 0 C to 60 C 32 F to 140 F Storage Temperature 45 C to 85 C 49 F to 185 F Humidity ...

Page 8: ...04 2018 Dimensions Isolation Module Indicator Module Panel Knockout Units inches mm The Indicator Module is designed for use with a standard 30 mm knockout with notch The notch should be positioned on top as shown in the image MOUNTING HOLES 3 Units inches mm Units inches mm ...

Page 9: ...ry or death Sensor leads of the same color should be terminated on the same conductor Each conductor should have at least one sensor lead set as shown on the schematic diagrams If a Sensor Lead separates from the termination point to the power conductor and contacts a low impedance path to ground the connectivity test can be defeated resulting in a false absence of voltage indication Ensure that a...

Page 10: ...N MANUAL VeriSafe AVT B21075_00 Page 9 of 20 04 2018 Single Phase 2 Wire PE Single Phase 2 Wire PE Redundant Detection Lead Single Phase 3 Wire PE Corner Grounded DELTA 3 Wire PE High Leg DELTA 3 Wire Neutral PE DC System 2 Wire PE ...

Page 11: ... Panduit Corp 2018 INSTRUCTION MANUAL VeriSafe AVT B21075_00 Page 10 of 20 04 2018 DC System 2 Wire PE Redundant Detection Lead ...

Page 12: ...e AVT is suitable for use on circuits delivering up to 300 000 rms symmetrical A at 600 V Use of Overcurrent Protection Installation of an AVT with overcurrent protection is neither required nor recommended When testing for the absence of a signal it is important to ensure that the tester is in direct contact with the circuit test point Installing overcurrent protection between the AVT and test po...

Page 13: ...ld pass This would be a multi fault scenario but is possible if terminations are not made properly and secured An AVT installed on a single phase system might only have one Detection Lead terminated to a power conductor If the Detection Lead were to become loose and make contact with a low impedance path to ground the connectivity test would pass However voltage would not be detected because the t...

Page 14: ... terminated properly and secured to the power conductor or other nearby rigid feature to prevent movement if the termination fails to remain intact Devices must be installed in an enclosure where the internal compartment is only accessible by the use of a tool or other mechanical means Before installation verify that after power is removed from the circuit to be monitored the potential measured be...

Page 15: ...or leads with a splice Use approved connection methods and follow local codes and standards when terminating the sensor leads Secure the sensor leads to the conductors to prevent the leads from contacting ground if the termination fails Refer to the Installation Considerations section for additional information 8 Route Sensor Leads and AVT System Cable to avoid sharp edges pinch points and prevent...

Page 16: ...n label Verify that the label is placed near the isolation module and marked to indicate where the AVT is installed Record changes to panel documentation Close panel and secure doors covers Press the Test Button to initiate the test The yellow Caution Indicator should flash rapidly to indicate the test is in progress followed by the Absence of Voltage Indicator illuminated green Review the Operati...

Page 17: ... of voltage push the Test Button A B Absence of Voltage Test Each time the Test Button is engaged the absence of voltage test sequence will be activated The test sequence includes running a self check using a known voltage source to test the tester to verify that the AVT is functioning testing for AC and DC voltage phase to phase and phase to ground and verifying the sensor leads are in contact wi...

Page 18: ...e test 2 Voltage detected above the threshold Warning This indicates that the enclosure is energized Follow safety procedures and use the appropriate PPE when investigating the source of voltage If panel has a stored energy source wait several minutes then re test to see if energy has dissipated 4 Proper installation of the sensor leads could not be verified Warning The enclosure may be energized ...

Page 19: ...r the area is known to be non hazardous Battery Replacement Follow these steps to replace the battery Table 1 provides a list of batteries approved for use with the AVT Do not discard the battery in the trash take it to an appropriate battery recycling facility Manufacturer Model Number Size Description Tadiran TL 5903 AA ER14505 3 6 Volt Lithium Battery Xeno Energy XLP 060F Saft LS14500 Table 1 A...

Page 20: ... alkaline cleaners Do not leave cleaners on the device for a long period rinse immediately Do not apply cleaners in direct sunlight or elevated temperatures The section of the VeriSafe Indicator Module that is external to the electrical enclosure is approved for wash down as specified by NEMA 4 IP66 and IP67 standards Before a wash down operation ensure the O rings are in good condition the facepl...

Page 21: ...nt to Buyer whichever is longer 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or services including any third party software or firmware which may be incorporated into a Panduit product and or resold or sublicensed by Panduit To the extent any warranties extended to Panduit by ...