Item
Unit
Indoor Unit
Pressure Vessel
Material
En-1.4521
Volume L
185
Design Pressure
Bar
10
Heat Exchanger
Material
EN-1.4521
Diameter mm
22
Thickness mm
0.8
Surface Area
m
2
1.8
Total Length
m
25
Note:
Cooling capacities are based on outdoor air temperature of 35°C Dry Bulb with controlled indoor water inlet
temperature of 12°C and water outlet temperature of 7°C.
Heating capacities are based on outdoor air temperature of 7°C Dry Bulb (44.6°F Dry Bulb), 6°C Wet Bulb
(42.8°F Wet Bulb) with controlled indoor water inlet temperature of 30°C and water outlet temperature of 35°C.
Specifications are subjected to change without prior notice for further improvement.
* Above 55°C, only possible with backup heater operation.
** Between outdoor ambient -10 °C and -15 °C, the water outlet temperature gradually decreases from 60 °C to
55 °C.
*** The sound pressure and sound power level is measured with distance 1.0m from the unit and height at 1.5m.
(Test carry out for cooling at ambient 35°C DB and Water Out 7°C, heating at ambient 7°C DB / 6°C WB and
water out 55°C)
**** The sound power level is measured with accordance to EN12102 under conditions of the EN14825.